Low Voltage Power Cable with PVC Insulation Yby-O; Yby-J

Low Voltage Power Cable with PVC Insulation Yby-O; Yby-J image
Get Latest Price Request a quote
You May Like
Product Details
Product Description
Low Voltage Power Cable with PVC Insulation YBY-O; YBY-J
Uo/U – 0.6/1 kV IEC 60502-1
Application:
YBY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are also used as control cables for transmission of measured values control and regulation pulses.
These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.
Cable construction | |
Construction | According to IEC 60502-1 |
Conductor | solid or multi-strand Cu wires class 1 or 2 acc. |
Insulation | IEC 60228 PVC acc. to IEC 60502 |
Core identification | single core-black, multiple core according to VDE 0293 |
Inner sheath | tapes and filling compound |
Armour | two steel tapes or two galvanized steel tapes |
Sheath | PVC type ST1 acc. IEC 60502 |
Color | black |
Technical data | |
Conductor resistance at 20°C | According to IEC 60228 class 1 or 2 |
Max. conductor temperature | +70°C |
Max. short circuit temperature | +160°C, not more than 5 sec |
Rated voltage Uo/U | 0.6/1 kV |
Test voltage | AC – 3.5 kV 50 Hz |
Bending radius -single core -multi core |
15 cable diameter 12 cable diameter |
Flame test | IEC 332 part 1 |
REFERENCE STANDARD
- Design Specification: IEC60502-1
- Conductor: IEC60228, BS EN60228
- Flame Retardancy: IEC60332-1, BS EN60332-1
INSTALLATION REFERENCE
- Minimum Bending Radius(mm): 8 x cable overall diameter
- Max. Pulling Tension (N/mm2) : 70ºC
Note :
Conductor Shape
1.5 – 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 – 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 – 50 sqmm supplied in wooden drum @ 1000 m
70 – 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%
Dimensions – number of cores x conductor cross-section | Construction | Construction of individual conductor | External diameter | Insulation thickness | Sheath thickness | Conductor resistance at 20 °C | Cu weight | Cable weight |
nominal | approx. | nominal | nominal | max. | approx. | |||
N x mm² | n x mm | mm | mm | mm | Ω/km | kg/km | kg/km | |
Power Cable YBY-J, YBY-O | ||||||||
2 x 1,5 | RE | 1 x 1,37 | 12,9 | 0,8 | 1,8 | 12,1 | 28,8 | 286 |
2 x 2,5 | RE | 1 x 1,74 | 13,7 | 0,8 | 1,8 | 7,41 | 48 | 423 |
2 x 4 | RE | 1 x 2,2 | 15,3 | 1 | 1,8 | 4,61 | 76,8 | 420 |
2 x 6 | RE | 1 x 2,7 | 16,3 | 1 | 1,8 | 3,08 | 115,2 | 493 |
2 x 10 | RM | 7 x 1,34 | 18,7 | 1 | 1,8 | 1,83 | 192 | 668 |
2 x 16 | RM | 7 x 1,70 | 20,9 | 1 | 1,8 | 1,15 | 307,2 | 873 |
2 x 25 | RM | 7 x 2,20 | 23,5 | 1,2 | 1,8 | 0,727 | 480 | 1201 |
2 x 35 | RM | 7 x 2,55 | 25,7 | 1,2 | 1,8 | 0,524 | 672 | 1480 |
2 x 50 | RM | 7 x 3,00 | 28,7 | 1,4 | 1,8 | 0,387 | 960 | 1881 |
2 x 70 | RM | 13 x 2,70 | 32,3 | 1,4 | 1,9 | 0,268 | 1344 | 2478 |
2 x 95 | RM | 17 x 2,70 | 37,9 | 1,6 | 2,1 | 0,193 | 1824 | 3378 |
2 x 120 | RM | 18 x 3,00 | 40,9 | 1,6 | 2,2 | 0,153 | 2304 | 4167 |
2 x 150 | RM | 22 x 3,00 | 44,9 | 1,8 | 2,3 | 0,124 | 2880 | 5091 |
2 x 185 | RM | 32 x 2,70 | 50,5 | 2 | 2,4 | 0,0991 | 3552 | 6272 |
2 x 240 | RM | 36 x 3,00 | 56,7 | 2,2 | 2,6 | 0,0754 | 4608 | 7945 |
2 x 300 | RM | 45 x 3,00 | 61,9 | 2,4 | 2,8 | 0,0601 | 5760 | 9628 |
3 x 1,5 | RE | 1 x 1,37 | 13,4 | 0,8 | 1,8 | 12,1 | 43,2 | 314 |
3 x 2,5 | RE | 1 x 1,74 | 14,3 | 0,8 | 1,8 | 7,41 | 72 | 371 |
3 x 4 | RE | 1 x 2,2 | 16 | 1 | 1,8 | 4,61 | 115,2 | 476 |
3 x 6 | RE | 1 x 2,7 | 17,1 | 1 | 1,8 | 3,08 | 172,8 | 569 |
3 x 10 | RM | 7 x 1,34 | 19,7 | 1 | 1,8 | 1,83 | 288 | 783 |
3 x 16 | RM | 7 x 1,70 | 22,1 | 1 | 1,8 | 1,15 | 460,8 | 1044 |
3 x 25 | RM | 7 x 2,20 | 24,9 | 1,2 | 1,8 | 0,727 | 720 | 1463 |
3 x 35 | SM | 7 x 2,55 | 27,3 | 1,2 | 1,8 | 0,524 | 1008 | 1822 |
3 x 50 | SM | 7 x 3,00 | 30,7 | 1,4 | 1,9 | 0,387 | 1440 | 2356 |
3 x 70 | SM | 13 x 2,70 | 34,6 | 1,4 | 2 | 0,268 | 2016 | 3136 |
3 x 95 | SM | 17 x 2,70 | 41,2 | 1,6 | 2,1 | 0,193 | 2736 | 4507 |
3 x 120 | SM | 18 x 3,00 | 43,5 | 1,6 | 2,2 | 0,153 | 3456 | 5251 |
3 x 150 | SM | 22 x 3,00 | 48 | 1,8 | 2,4 | 0,124 | 4320 | 6496 |
3 x 185 | SM | 32 x 2,70 | 54 | 2 | 2,5 | 0,0991 | 5328 | 7972 |
3 x 240 | SM | 36 x 3,00 | 60,7 | 2,2 | 2,7 | 0,0754 | 6912 | 10140 |
3 x 300 | SM | 45 x 3,00 | 66,3 | 2,4 | 2,9 | 0,0601 | 8640 | 12349 |
3 x 16+10 | RM/RE | 7 x 1,7/7 x 1,3 | 23,2 | 1,0 / 1,0 | 1,8 | 1,15 | 556,8 | 1163 |
3 x 25+16 | RM/RM | 7 x 2,2/7 x 1,7 | 26,2 | 1,2 / 1,0 | 1,8 | 0,727 | 873,6 | 1641 |
3 x 35+16 | SM/RM | 7 x 2,5/7 x 1,7 | 28,2 | 1,2 / 1,0 | 1,8 | 0,524 | 1161,6 | 1978 |
3 x 50+25 | SM/RM | 7 x 3,/7 x 2,2 | 31,9 | 1,4 / 1,2 | 1,9 | 0,387 | 1680 | 2606 |
3 x 70+35 | SM/RM | 13 x 2,7/7 x 2,5 | 35,8 | 1,4 / 1,2 | 2 | 0,268 | 2352 | 3471 |
3 x 95+50 | SM/RM | 17 x 2,7/7 x 3 | 42,6 | 1,6 / 1,4 | 2,2 | 0,193 | 3216 | 4963 |
3 x 120+70 | SM/RM | 18 x 3/13 x 2,7 | 45,6 | 1,6 / 1,4 | 2,3 | 0,153 | 4128 | 5928 |
3 x 150+70 | SM/RM | 22 x 3/13 x 2,7 | 49,3 | 1,8 / 1,4 | 2,4 | 0,124 | 4992 | 7065 |
3 x 185+95 | SM/RM | 32 x 2,7/17 x 2,7 | 56,1 | 2,0 / 1,6 | 2,6 | 0,0991 | 6240 | 8866 |
3 x 240+120 | SM/RM | 36 x 3/18 x 3 | 62,4 | 2,2 / 1,6 | 2,8 | 0,0754 | 8064 | 11155 |
3 x 300+150 | SM/RM | 45 x 3/22 x 3 | 68,3 | 2,4 / 1,8 | 3 | 0,0601 | 10080 | 13649 |
4 x 1,5 | RE | 1 x 1,37 | 14,2 | 0,8 | 1,8 | 12,1 | 57,6 | 357 |
4 x 2,5 | RE | 1 x 1,74 | 15,1 | 0,8 | 1,8 | 7,41 | 96 | 424 |
4 x 4 | RE | 1 x 2,2 | 17,1 | 1 | 1,8 | 4,61 | 153,6 | 555 |
4 x 6 | RE | 1 x 2,7 | 18,3 | 1 | 1,8 | 3,08 | 230,4 | 670 |
4 x 10 | RM | 7 x 1,34 | 21,2 | 1 | 1,8 | 1,83 | 384 | 936 |
4 x 16 | RM | 7 x 1,70 | 23,8 | 1 | 1,8 | 1,15 | 614,4 | 1265 |
4 x 25 | RM | 7 x 2,20 | 27 | 1,2 | 1,8 | 0,727 | 960 | 1793 |
4 x 35 | SM | 7 x 2,55 | 29,6 | 1,2 | 1,8 | 0,524 | 1344 | 2249 |
4 x 50 | SM | 7 x 3,00 | 33,6 | 1,4 | 2 | 0,387 | 1920 | 2943 |
4 x 70 | SM | 13 x 2,70 | 38,7 | 1,4 | 2,1 | 0,268 | 2688 | 4172 |
4 x 95 | SM | 17 x 2,70 | 45,4 | 1,6 | 2,3 | 0,193 | 3648 | 5671 |
4 x 120 | SM | 18 x 3,00 | 48 | 1,6 | 2,4 | 0,153 | 4608 | 6631 |
4 x 150 | SM | 22 x 3,00 | 53 | 1,8 | 2,6 | 0,124 | 5760 | 8205 |
4 x 185 | SM | 32 x 2,70 | 59,6 | 2 | 2,7 | 0,0991 | 7104 | 10092 |
4 x 240 | SM | 36 x 3,00 | 67 | 2,2 | 2,9 | 0,0754 | 9216 | 12866 |
4 x 300 | SM | 45 x 3,00 | 73,2 | 2,4 | 3,1 | 0,0601 | 11520 | 15705 |
5 x 1,5 | RE | 1 x 1,37 | 15 | 0,8 | 1,8 | 12,1 | 72 | 401 |
5 x 2,5 | RE | 1 x 1,74 | 16,1 | 0,8 | 1,8 | 7,41 | 120 | 483 |
5 x 4 | RE | 1 x 2,2 | 18,3 | 1 | 1,8 | 4,61 | 192 | 640 |
5 x 16 | RM | 7 x 1,70 | 25,8 | 1 | 1,8 | 1,15 | 768 | 1472 |
5 x 50 | SM | 7 x 3,00 | 37 | 1,4 | 2,1 | 0,387 | 2400 | 3498 |
5 x 70 | SM | 13 x 2,70 | 42,6 | 1,4 | 2,2 | 0,268 | 3360 | 4956 |
5 x 95 | SM | 17 x 2,70 | 50 | 1,6 | 2,4 | 0,193 | 4560 | 6748 |
5 x 120 | SM | 18 x 3,00 | 53,1 | 1,6 | 2,6 | 0,153 | 5760 | 7941 |
*Further information about rating factor for certain cable arrangement can be found on supplementary technical information.
More information and other cable inquiry, pls contact Vivian Yuan as follows:
Vivian Yuan
We are China Low Voltage Power Cable with PVC Insulation Yby-O; Yby-J manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Tags: Copper Cable, Henan Hongda Cable Co., Ltd., Power Cable