0.6/1kV 7 Core 0.75mm2 KVV Control Cable
- Application
Wiring for controlling electrical equipment and instrument meters, monitoring and controlling return circuit, protecting and measuring in power distribution with rated voltage up to 450/750V(0.6/1KV) A.C .For the operation and control of automation and interconnection between switchboard and machine, including tool machines.
- Standards
GB/T9330-2008 ,IEC 60502, etc. we can also design and produce for special application requirement.
- Operating features
- The maximum permissible continuous operating temperature is 70ºC
- The lowest installation temperature of the cable is 0ºC .
- Permissible Min. Bending radius not less than 6 times of the
completed cable diameter for unarmoured cable; not less than 12 times of the completed cable
diameter for armoured or copper tape screened cable; not less than 6 times of the completed cable diameter for screened fle xible cable.
- Type, descriptions and applications
Chinese Type | Descriptions | Applications |
KVV | Copper conductor PVC insulated PVC sheathed control cables | For laying indoor, in tunnels, ducts, conduit etc. Permanent place |
KVVR | Copper conductor PVC insulated and sheathed flexible control cable | For laying indoor ,in tunnels, ducts and movable using |
KVVP | Copper conductor PVC insulated and sheathed copper wire braiding shielded control cable | For laying indoor, in tunnels, ducts, conduit etc. permanent place where shield required. |
KVVRP | Copper conductor PVC insulated and sheathed copper wire braiding shielded flexible control cable | For laying indoor ,in tunnels, ducts and flexible and shield required etc.place ,easy to move |
KVVP2 | Copper conductor PVC insulated PVC sheathed copper tape shielded control cables | For laying indoor, in tunnels, ducts, conduit etc. permanent place where shield required. |
KVVP2-22 | Copper conductor PVC Insulated PVC Sheathed Copper Tape shielded steel tape armored Control Cables | Used in light-current control system and heavy-current magnetic interference region. |
KVV22 |
Copper conductor PVC insulated PVC sheathed steel tape armored control cables | For laying indoor, in tunnels, ducts, conduit and direct burial etc. Permanent place, able to bear greater mechanical force |
KVV32 |
Copper conductor PVC insulated PVC sheathed steel wire armored control cables | For laying indoor, in tunnels, ducts, conduit and direct burial etc. Permanent place, able to bear greater mechanical force |
NOTE:Hongda cable company can produce “Flame-Retardant Series”, “Fire-Resistant Series”, “Low Smoke Halogen Free (LSHF/LSOH) Series”, “Low Smoke Low Halogen (LSLH) Series”, etc. control cable as customer required. Performance in line with IEC60332: 2004 requirements.
- Production range
Type | Rated voltage U0/U | Nominal conductor cross section (mm2) | Standards | ||||||
0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | |||
Number of cores | |||||||||
KVV |
450/750V |
2~61 | 2~14 | 2~10 |
GB/T9330-2008 |
||||
KVVR KVVRP | 2~61 | – | – | ||||||
KVVP2 KVVP | 4~61 | 4~14 | 4~10 | ||||||
KVV22,KVV32, KVVP2-22 |
7~61 | 4~61 | 4~14 | 4~10 |
Note::Recommended core numbers are 2,3,4,5,7,8,10,12,14,49,24,27,30,37and 61 Construction size and Properties of cable
-
- KVVR type, 450/750V(0.6/1kV) Copper Conductor PVC Insulated and Sheathed Control Cable to GB/T9330-2008
Number of cores×Nominal cross section mm2 |
Nominal thickness of insulation mm | Nominal sheath thickness mm |
Average overall diameter mm | Max.DC resistance of conductor at 20 ºC Ω/km | Approx. Weightof cable kg/km | |
Limit | Caps | |||||
2×0.75 | 0.6 | 1.2 | 6.7 | 8.1 | 26.0 | 62.8 |
2×1.0 | 0.6 | 1.2 | 7.0 | 8.5 | 19.5 | 70.2 |
2×1.5 | 0.7 | 1.2 | 7.9 | 9.5 | 13.3 | 88.5 |
2×2.5 | 0.8 | 1.2 | 9.0 | 10.9 | 7.98 | 124.3 |
2×4 | 0.8 | 1.2 | 9.9 | 11.9 | 4.95 | 160.2 |
2×6 | 0.8 | 1.2 | 10.8 | 13.1 | 3.30 | 211.3 |
2×10 | 1.0 | 1.7 | 14.3 | 17.3 | 1.91 | 362.8 |
3×0.75 3×1.0 3×1.5 3×2.5 3×4 3×6 3×10 |
0.6 0.6 0.7 0.8 0.8 0.8 1.0 |
1.2 1.2 1.2 1.2 1.2 1.5 1.7 |
7.1 7.4 8.3 9.5 10.5 11.5 15.2 |
8.5 8.9 10.0 11.5 12.7 13.9 18.4 |
26.0 19.5 13.3 7.98 4.95 3.30 1.91 |
78.3 88.5 113.7 156.9 208.5 300.4 487.4 |
4×0.75 4×1.0 4×1.5 4×2.5 4×4 4×6 4×10 |
0.6 0.6 0.7 0.8 0.8 0.8 1.0 |
1.2 1.2 1.2 1.2 1.5 1.5 1.7 |
7.6 7.9 9.0 10.4 11.4 13.2 16.6 |
9.2 9.6 10.9 12.5 13.8 15.9 20.1 |
26.0 19.5 13.3 7.98 4.95 3.30 1.91 |
93.2 106.3 138.7 202.2 283.9 385.4 615.6 |
5×0.75 5×1.0 5×1.5 5×2.5 5×4 5×6 5×10 |
0.6 0.6 0.7 0.8 0.8 0.8 1.0 |
1.2 1.2 1.2 1.5 1.5 1.5 1.7 |
8.2 8.6 9.7 11.3 13.0 14.3 18.2 |
9.9 10.3 11.7 13.6 15.7 17.3 22.0 |
26.0 19.5 13.3 7.98 4.95 3.30 1.91 |
106.3 122.5 162.1 253.5 344.3 454.3 750.2 |
7×0.75 7×1.0 7×1.5 7×2.5 7×4 7×6 7×10 |
0.6 0.6 0.7 0.8 0.8 0.8 1.0 |
1.2 1.2 1.2 1.5 1.5 1.5 1.7 |
8.8 9.2 10.5 12.8 14.1 15.6 20.3 |
10.6 11.1 12.7 15.5 17.1 18.8 24.5 |
26.0 19.5 13.3 7.98 4.95 3.30 1.91 |
129.2 151.1 204.4 317.0 433.8 585.0 963.0 |
8×0.75 8×1.0 8×1.5 8×2.5 8×4 8×6 8×10 |
0.6 0.6 0.7 0.8 0.8 0.8 1.0 |
1.2 1.2 1.5 1.5 1.5 1.7 1.7 |
9.7 10.2 11.7 14.3 15.8 17.4 22.8 |
11.7 12.3 14.1 17.2 19.0 21.0 27.5 |
26.0 19.5 13.3 7.98 4.95 3.30 1.91 |
144.6 169.4 247.6 357.0 490.1 679.3 1076.8 |
10×0.75 10×1.0 10×1.5 10×2.5 10×4 10×6 |
0.6 0.6 0.7 0.8 0.8 0.8 |
1.5 1.5 1.5 1.5 1.7 1.7 |
10.8 11.4 13.7 16.0 17.8 20.1 |
13.1 13.8 16.6 19.4 21.5 24.2 |
26.0 19.5 13.3 7.98 4.95 3.30 |
193.4 225.2 303.2 439.5 623.3 849.1 |
Number of cores×Nominal cross section mm2 |
Nominal thickness of insulation mm |
Nominal sheath thickness mm |
Average.overall diameter mm | Max.DC resistance of conductor at 20 ºC Ω/km | Approx. Weightof cable kg/km | |
Limit | Caps | |||||
12×0.75 | 0.6 | 1.5 | 11.2 | 13.5 | 26.0 | 218.8 |
12×1.0 | 0.6 | 1.5 | 11.8 | 14.2 | 19.5 | 256.3 |
12×1.5 | 0.7 | 1.5 | 14.2 | 17.1 | 13.3 | 347.8 |
12×2.5 | 0.8 | 1.5 | 16.5 | 20.0 | 7.98 | 508.5 |
12×4 | 0.8 | 1.7 | 18.7 | 22.6 | 4.95 | 723.8 |
12×6 | 0.8 | 1.7 | 20.7 | 25.0 | 3.30 | 981.2 |
14×0.75 | 0.6 | 1.5 | 11.7 | 14.1 | 26.0 | 246.0 |
14×1.0 | 0.6 | 1.5 | 12.9 | 15.6 | 19.5 | 289.2 |
14×1.5 | 0.7 | 1.5 | 14.8 | 17.9 | 13.3 | 394.5 |
14×2.5 | 0.8 | 1.5 | 17.4 | 21.0 | 7.98 | 580.0 |
14×4 | 0.8 | 1.7 | 19.6 | 23.7 | 4.95 | 827.7 |
14×6 | 0.8 | 1.7 | 21.8 | 26.3 | 3.30 | 1126.1 |
16×0.75 16×1.0 16×1.5 16×2.5 |
0.6 0.6 0.7 0.8 |
1.5 1.5 1.5 1.7 |
12.9 13.5 15.6 18.3 |
15.5 16.4 18.8 22.1 |
26.0 19.5 13.3 7.98 |
273.5 322.5 441.7 670.7 |
19×0.75 19×1.0 19×1.5 19×2.5 |
0.6 0.6 0.7 0.8 |
1.5 1.5 1.5 1.7 |
13.5 14.2 16.4 19.6 |
16.3 17.2 19.8 23.7 |
26.0 19.5 13.3 7.98 |
312.8 370.3 509.9 776.8 |
24×0.75 24×1.0 24×1.5 24×2.5 |
0.6 0.6 0.7 0.8 |
1.5 1.5 1.7 1.7 |
15.6 16.4 19.4 22.8 |
18.8 19.8 23.4 27.6 |
26.0 19.5 13.3 7.98 |
386.2 458.4 653.0 967.6 |
27×0.75 27×1.0 27×1.5 27×2.5 |
0.6 0.6 0.7 0.8 |
1.5 1.5 1.7 1.7 |
15.9 16.7 19.8 23.3 |
19.2 20.2 23.9 28.2 |
26.0 19.5 13.3 7.98 |
423.2 503.7 718.6 1069.6 |
30×0.75 30×1.0 30×1.5 30×2.5 |
0.6 0.6 0.7 0.8 |
1.7 1.7 1.7 1.7 |
16.4 17.5 20.0 24.0 |
19.8 21.0 24.0 28.0 |
26.0 19.5 13.3 7.98 |
478.4 568.3 786.7 1174.6 |
37×0.75 37×1.0 37×1.5 37×2.5 |
0.6 0.6 0.7 0.8 |
1.7 1.7 1.7 1.7 |
18.0 19.0 22.0 26.1 |
21.5 23.0 26.6 31.5 |
26.0 19.5 13.3 7.98 |
569.4 679.2 945.1 1419.0 |
Control cables – VDE standards
the full portfolio of flexible control cables manufactured in accordance with VDE0250 standards, which includes:
YY cable (YSLY) | Versatile unscreened or unshielded cable suitable for most situations where there is only light mechanical stress |
CY cable (YSLCY) | Multicore screened flexible cable with Polyethylene Terephthalate (PETP) for electromagnetic interference free-transmission |
SY cable (YSLYSY) | Flexible shielded cable with galvanised steel wire braid for additional mechanical protection |
LiYCY cable | Screened and shielded cable for applications where moderate mechanical stress and electromagnetic screening is required |
LiYY cable | Unscreened and unshielded cable for light duty in dry and humid environments |
LiHH cable | Unscreened LSZH low capacitance control |
LiHCH cable | Screened LSZH data transmission cable |
Depending on their construction properties, these flexible cables can be suitable for use under light, medium or high mechanical stresses. They also offer various degrees of protection against electrical interference and resistance to caustic substances and oils.
CY cables, SY cables and YY cables are not suitable for fixed wiring applications requiring compliance with the requirements set out in BS7671.
Packaging&Delivery
Packaging Details: Packing Length:100m/roll, 200m/roll, 305m/roll, 500m/roll
Delivery Time:Normally within 10 days (detailly depend on the order quantity)
Contact us
Looking forward to cooperation with you.If you have any question or need our certification and sample.Pls contact me freely.You can talk with me by Email or chat software.
We are China 7 Cores 0.75mm2 1.5mm2 2.5mm2 Kvv/Kvvr Control Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Tags: 7*1.5mm2, Control Cable, Henan Hongda Cable Co., Ltd.