H05VV-F, H03VV-F Electrica Wire PVC Insulation Power Cable

China H05VV-F, H03VV-F Electrica Wire PVC Insulation Power Cable  manufacture and supplier

H05VV-F, H03VV-F Electrica Wire PVC Insulation Power Cable image

Get Latest Price Request a quote

You May Like

Product Details

Model NO.
H05VV-f, H03VV-f
Application
Overhead
Conductor Material
Copper
Sheath Material
PVC
Insulation Material
PVC
Material Shape
Round Wire
Range of Application
Power Transmission
Certification
ISO9001, CE, CCC, RoHS, VDE
Brand
QIFAN
Length of Per Package
100meters
Color of The Cores
Red, Blue, Grown, Yellow, etc
Flame Retardant
Yes
Leadtime
15days
Transport Package
Reel
Specification
as per requirements
Trademark
Qifan
Origin
China
HS Code
8544492100
Production Capacity
1000000000 Meters Per Year

Product Description

Product Parameters

Copper Conductor PVC Insulation Electrical Wire (H07V-U,H07V-R,H07V-K)

DIN VDE 0281-3, BS6004, HD 21.3, IEC60227

CONSTRUCTION
Conductors Annealed Copper Conductor acc.  to IEC 60228:
Class 1 solid H07V-U,
Class 2 stranded H07V-R,
Class 5 Flexible H07V-K
Insulation PVC
Color of Insulation Green/Yellow, Blue, Black, Brown or other colors

 

CHARACTERISTICS
Maximum Conductor operating temperature: +70ºC
Lowest ambient temperature for fixed installation:-30ºC
Lowest installation temperature: -5ºC
Maximum short-circuit conductor temperature:+160ºC
Test voltage:2500V
Flame retardant: IEC60332
Minimum Bending radius For cable diameter D (mm)
  D≤8 8<D≤12 12<D≤20 D>20
Normal use 4D 5D 6D 6D
Careful bending at termination 2D 3D 4D 4D

 

APPLICATIONS
Installation in surface mounted or embedded conduits, or similar closed systems. Suitable for fixed protected installation in, or on lighting or control gear for voltages up to 1000 a.c. or, up to 750V D.C. to earth. 
Standard length cable packing 50m or 100m in rings or on spools, or 500m on drums. Other forms of packing and delivery are available on request.
Number and cross-sectional area of conductor Approximate overall diameter Approximate net weight of cables Maximum conductor resistance at 20ºC Minimum insulation resistance at
temperature 70ºC
n x mm2 mm Kg/km Ω/km MΩ.km
H07V-U
1.5 2.7 20 12.1 0.011
2.5 3.3 31 7.41 0.010
4 3.7 45 4.61 0.0087
6 4.2 63 3.08 0.0074
10 5.4 105 1.83 0.0072
H07V-R
Number and cross-sectional area of conductor Approximate overall diameter Approximate net weight of cables Maximum conductor resistance at 20ºC Minimum insulation resistance at
temperature 70ºC
n x mm2 mm Kg/km Ω/km MΩ.km
1.5 3.0 21 12.1 0.010
2.5 3.6 33 7.41 0.0099
4 4.1 48 4.61 0.0082
6 4.5 66 3.08 0.0070
10 5.8 110 1.83 0.0067
16 6.8 167 1.15 0.0056
25 8.5 262 0.727 0.0053
35 9.6 353 0.524 0.0046
50 11.3 480 0.387 0.0046
70 12.6 672 0.268 0.0040
95 15.0 932 0.193 0.0039
120 16.4 1158 0.153 0.0035
150 18.4 1432 0.124 0.0035
185 20.3 1789 0.0991 0.0035
240 23.2 2325 0.0754 0.0034
300 25.4 2908 0.0601 0.0033
400 28.5 3756 0.0470 0.0031

 

H07V-K
Number and cross-sectional area of conductor Approximate overall diameter Approximate net weight of cables Maximum conductor resistance at 20ºC Minimum insulation resistance at
temperature 70ºC
n x mm2 mm Kg/km Ω/km MΩ.km
1.0 2.77 20 19.5 0.010
1.5 2.9 20 13.3 0.010
2.5 3.6 31 7.98 0.0095
4 4.1 45 4.95 0.0078
6 4.6 63 3.30 0.0068
10 6.0 107 1.91 0.0065
16 7.1 161 1.21 0.0053
25 8.7 247 0.780 0.0050
35 9.8 344 0.554 0.0043
50 11.8 483 0.386 0.0042
70 13.6 669 0.272 0.0036
95 16.1 886 0.206 0.0036
120 17.2 1111 0.161 0.0032
150 19.4 1389 0.129 0.0032
185 22.1 1697 0.106 0.0032
240 24.0 2210 0.0801 0.0031

We are China H05VV-F, H03VV-F Electrica Wire PVC Insulation Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Tags: , , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION