Canada C. S. a Certificated Urd 5~46kv Concentric Neutral Power Cable Aluminum Core with 133% Insulation Level

Canada C. S. a Certificated Urd 5~46kv Concentric Neutral Power Cable Aluminum Core with 133% Insulation Level image
Get Latest Price Request a quote
You May Like
Product Details
Product Description
TOP TEN CABLE MANUFACTURER IN CHINA
LARGEST CABLE MANUFACTUER IN NORTH CHINA
ANNUAL EXPORT VOLUME EXCEED 500MILLION USD
WITH UL,TUV,KEMA,CE,BV,PSB,SABS,LLOYD’S,GL,NK,KR,ABS PRODUCTS CERTIFICATIONS
WITH TUV TYPE TESTING REPORT
WIDE PRODUCTS RANGE
ISO9001,ISO18001,OHSAS18001 SYSTEM CERTIFICATIONS
CNAS APPROVAL LABROTARY
Canada C.S.A Certificated URD 5~46kv Concentric Neutral Power Cable Aluminum Core with 133% Insulation Level
Product Description
Standard
UL 1072 Medium Voltage Power Cables. CSA C68.5
ICEA S-93-639/NEMA WC74 5 kV – 46 kV Shielded Power Cables.
ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5 kV – 46 kV.
Cable Construction
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset crosslinked polyethylene (XLPE). On request, TR-XLPE/EPR
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Solid soft annealed uncoated copper wires per ASTM B3, helically applied and uniformly spaced. On request, copper tape shield.
6. Binder Tape: A suitable tape, as required.
7. Jacket: Black sunlight resistance and flame retardant polyvinyl chloride (PVC) compound. Configuration Options: On request, LLDPE/ XLPE
Cable Parameters
Size AWG |
Number of Strands |
Conductor Nominal OD |
100% Insulation Levels (90 mil) |
||||
|
|
|
Nominal diameter over Insulation |
Jacket Thickness |
Approximate Outside Diameter |
Approximate Net Weight |
|
|
|
|
|
|
|
Copper |
Aluminum |
or kcmil |
|
in |
mil |
mil |
in |
lb/kft |
lb/kft |
8 |
7 |
0.13 |
0.35 |
60 |
0.56 |
200 |
– |
6 |
7 |
0.17 |
0.38 |
60 |
0.59 |
245 |
188 |
4 |
7 |
0.21 |
0.43 |
60 |
0.64 |
311 |
221 |
2 |
7 |
0.27 |
0.48 |
60 |
0.69 |
410 |
267 |
1 |
19 |
0.3 |
0.51 |
60 |
0.72 |
475 |
295 |
1/0 |
19 |
0.34 |
0.55 |
60 |
0.76 |
558 |
331 |
2/0 |
19 |
0.38 |
0.59 |
60 |
0.8 |
659 |
373 |
3/0 |
19 |
0.42 |
0.64 |
80 |
0.89 |
821 |
460 |
4/0 |
19 |
0.48 |
0.69 |
80 |
0.94 |
980 |
526 |
250 |
37 |
0.52 |
0.75 |
80 |
0.99 |
1124 |
586 |
350 |
37 |
0.62 |
0.84 |
80 |
1.09 |
1477 |
724 |
500 |
37 |
0.74 |
0.96 |
80 |
1.21 |
1996 |
921 |
750 |
61 |
0.91 |
1.14 |
80 |
1.41 |
2879 |
1266 |
1000 |
61 |
1.06 |
1.3 |
80 |
1.57 |
3723 |
1573 |
Technical Specification
Phase Conductor | Neutral | Thickness Per Cond. (mils) | Diameter (mils) | Weight 1000 feet (lbs.) | |||||||
Size (AWG or kcmil) | Stranding | No. of Wires | Size (AWG) | Nominal Insul. | Insul. Shield min. Point | Approx. Jkt. | Bare Phase Cond. | Over Insul. | Over Insul. Shield | Comp. Cable | Comp. Cable |
ALUMINUM CONDUCTOR – 0.345 INSULATION – 100% INSULATION LEVEL ” FULL COPPER WIRE NEUTRAL | |||||||||||
1*1/0 | 19 | 16 | 14 | 345 | 40 | 55 | 335 | 1066 | 1176 | 1414 | 977 |
1*2/0 | 19 | 13 | 12 | 345 | 40 | 55 | 376 | 1107 | 1217 | 1488 | 1123 |
1*3/0 | 19 | 16 | 12 | 345 | 40 | 55 | 423 | 1153 | 1263 | 1534 | 1249 |
1*4/0 | 19 | 13 | 10 | 345 | 40 | 80 | 474 | 1212 | 1322 | 1686 | 1537 |
1*250 | 37 | 15 | 10 | 345 | 40 | 80 | 523 | 1261 | 1371 | 1735 | 1678 |
1*300 | 37 | 18 | 10 | 345 | 40 | 80 | 572 | 1310 | 1420 | 1784 | 1858 |
1*350 | 37 | 21 | 10 | 345 | 40 | 80 | 617 | 1355 | 1465 | 1829 | 2034 |
1*400 | 37 | 19 | 9 | 345 | 40 | 80 | 661 | 1399 | 1509 | 1898 | 2243 |
1*450 | 37 | 21 | 9 | 345 | 40 | 80 | 701 | 1439 | 1549 | 1938 | 2400 |
1*500 | 37 | 19 | 8 | 345 | 40 | 80 | 738 | 1476 | 1586 | 2003 | 2626 |
1*550 | 61 | 21 | 8 | 345 | 55 | 80 | 783 | 1527 | 1657 | 2074 | 2859 |
1*600 | 61 | 23 | 8 | 345 | 55 | 80 | 817 | 1561 | 1691 | 2108 | 3033 |
1*650 | 61 | 25 | 8 | 345 | 55 | 80 | 850 | 1594 | 1724 | 2141 | 3205 |
1*700 | 61 | 26 | 8 | 345 | 55 | 80 | 883 | 1627 | 1757 | 2174 | 3332 |
1*750 | 61 | 28 | 8 | 345 | 55 | 80 | 914 | 1658 | 1788 | 2205 | 3502 |
1*800 | 61 | 30 | 8 | 345 | 55 | 80 | 943 | 1687 | 1817 | 2234 | 3671 |
ALUMINUM CONDUCTOR – 0.345 INSULATION – 100% INSULATION LEVEL ” 1/3 COPPER WIRE NEUTRAL | |||||||||||
1*1/0 | 19 | 6 | 14 | 345 | 40 | 55 | 335 | 1066 | 1176 | 1414 | 859 |
1*2/0 | 19 | 7 | 14 | 345 | 40 | 55 | 376 | 1107 | 1217 | 1455 | 928 |
1*3/0 | 19 | 9 | 14 | 345 | 40 | 55 | 423 | 1153 | 1263 | 1501 | 1021 |
1*4/0 | 19 | 11 | 14 | 345 | 40 | 55 | 474 | 1212 | 1322 | 1561 | 1136 |
1*250 | 37 | 13 | 14 | 345 | 40 | 55 | 523 | 1261 | 1371 | 1609 | 1237 |
1*300 | 37 | 15 | 14 | 345 | 40 | 80 | 572 | 1310 | 1420 | 1708 | 1405 |
1*350 | 37 | 18 | 14 | 345 | 40 | 80 | 617 | 1355 | 1465 | 1754 | 1525 |
1*400 | 37 | 13 | 12 | 345 | 40 | 80 | 661 | 1399 | 1509 | 1831 | 1682 |
1*450 | 37 | 14 | 12 | 345 | 40 | 80 | 701 | 1439 | 1549 | 1870 | 1780 |
1*500 | 37 | 16 | 12 | 345 | 40 | 80 | 738 | 1476 | 1586 | 1907 | 1896 |
1*550 | 61 | 18 | 12 | 345 | 55 | 80 | 783 | 1527 | 1657 | 1979 | 2067 |
1*600 | 61 | 19 | 12 | 345 | 55 | 80 | 817 | 1561 | 1691 | 2013 | 2163 |
1*650 | 61 | 13 | 10 | 345 | 55 | 80 | 850 | 1594 | 1724 | 2088 | 2333 |
1*700 | 61 | 14 | 10 | 345 | 55 | 80 | 883 | 1627 | 1757 | 2121 | 2440 |
1*750 | 61 | 15 | 10 | 345 | 55 | 80 | 914 | 1658 | 1788 | 2152 | 2545 |
1*800 | 61 | 16 | 10 | 345 | 55 | 80 | 943 | 1687 | 1817 | 2181 | 2648 |
1*900 | 61 | 18 | 10 | 345 | 55 | 80 | 1001 | 1745 | 1875 | 2239 | 2854 |
1*1000 | 61 | 20 | 10 | 345 | 55 | 80 | 1055 | 1800 | 1930 | 2293 | 3058 |
1*1250 | 61 | 20 | 9 | 345 | 55 | 80 | 1180 | 1924 | 2054 | 2443 | 3606 |
We are China Canada C. S. a Certificated Urd 5~46kv Concentric Neutral Power Cable Aluminum Core with 133% Insulation Level manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Tags: Aluminum Conductor 35kv Urd, Hebei Huatong Wires & Cables Group Co., Ltd., Mv-90 & Mv-105 Power Cable