35mm2 Aluminum Alloy AAAC Conductor
1. Application
AAAC Conductor is used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics.
1). AAAC conductors are extensively used for overhead distribution and transmission lines adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction.
2). The aluminum alloy conductors are used in replace of single-layer ACSR conductors to reduce power loss in overhead distribution and transmission lines, when replacing the aluminum conductor steel reinforced, the AAAC can save 5-8% of the construction cost.
3). AAAC referred to have higher strength but lower conductivity than pure aluminum being lighter, alloy conductors can sometimes be used to advantage in replace of the more conventional ACSR.2. Standard
2. Standard
ASTM B399, BS EN 50183, BS 3234, DIN 48201, IEC 61089, and ect.
3. Specification
AAAC Conductor according to ASTM B399
Code Name | Area | Size & Stranding of ACSR with Equal Diameter | No. & Diameter of wires | Overall Diameter | Weight | Nominal Breaking Load | ||
Nominal | Actual | |||||||
MCM | mm2 | AWG or MCM | Al/Steel | mm | mm | kg/km | kN | |
Akron | 30.58 | 15.48 | 6 | 6/1 | 7/1.68 | 5.04 | 42.7 | 4.92 |
Alton | 48.69 | 24.71 | 4 | 6/1 | 7/2.12 | 6.35 | 68.0 | 7.84 |
Ames | 77.47 | 39.22 | 2 | 6/1 | 7/2.67 | 8.02 | 108 | 12.45 |
Azusa | 123.3 | 62.38 | 1/0 | 6/1 | 7/3.37 | 10.11 | 172 | 18.97 |
Anaheim | 155.4 | 78.65 | 2/0 | 6/1 | 7/3.78 | 11.35 | 217 | 23.93 |
Amherst | 195.7 | 99.22 | 3/0 | 6/1 | 7/4.25 | 12.75 | 273 | 30.18 |
Alliance | 246.9 | 125.1 | 4/0 | 6/1 | 7/4.77 | 14.31 | 345 | 38.05 |
Butte | 312.8 | 158.6 | 266.8 | 26/7 | 19/3.26 | 16.30 | 437 | 48.76 |
Canton | 394.5 | 199.9 | 336.4 | 26/7 | 19/3.66 | 18.30 | 551 | 58.91 |
Cairo | 465.4 | 235.8 | 397.5 | 26/7 | 19/3.98 | 19.88 | 650 | 69.48 |
Darien | 559.5 | 283.5 | 477.0 | 26/7 | 19/4.36 | 21.79 | 781 | 83.52 |
Elgin | 652.4 | 330.6 | 556.5 | 26/7 | 19/4.71 | 23.54 | 911 | 97.42 |
Flint | 740.8 | 375.3 | 636.0 | 26/7 | 37/3.59 | 25.16 | 1035 | 108.21 |
Greely | 927.2 | 469.8 | 795.0 | 26/7 | 37/4.02 | 28.14 | 1295 | 135.47 |
AAAC Conductor according to DIN 48201
Code number | Calculated area | Number of wires | Diameter of wire | Overall diameter of conductor | Linear mass | Rated tensile strength | Max. DC resistance at 20ºC |
mm2 | mm2 | mm | mm | kg/km | daN | Ω/km | |
16 | 15.89 | 7 | 1.70 | 5.1 | 43 | 444 | 2.0910 |
25 | 24.25 | 7 | 2.10 | 6.3 | 66 | 677 | 1.3703 |
35 | 34.36 | 7 | 2.50 | 7.5 | 94 | 960 | 0.9669 |
50 | 49.48 | 7 | 3.00 | 9.0 | 135 | 1382 | 0.6714 |
50 | 48.35 | 19 | 1.80 | 9.0 | 133 | 1350 | 0.6905 |
70 | 65.81 | 19 | 2.10 | 10.5 | 181 | 1838 | 0.5073 |
95 | 93.27 | 19 | 2.50 | 12.5 | 256 | 2605 | 0.3579 |
120 | 116.99 | 19 | 2.80 | 14.0 | 322 | 3268 | 0.2854 |
150 | 147.11 | 37 | 2.25 | 15.8 | 406 | 4109 | 0.2274 |
185 | 181.62 | 37 | 2.50 | 17.5 | 500 | 5073 | 0.1842 |
240 | 242.54 | 61 | 2.25 | 20.3 | 670 | 6774 | 0.1383 |
300 | 299.43 | 61 | 2.50 | 22.5 | 827 | 8363 | 0.1120 |
400 | 400.14 | 61 | 2.89 | 26.0 | 1104 | 11176 | 0.0838 |
500 | 499.63 | 61 | 3.23 | 29.1 | 1379 | 13960 | 0.06709 |
625 | 626.20 | 91 | 2.96 | 32.6 | 1732 | 17490 | 0.0540 |
800 | 802.09 | 91 | 3.35 | 36.9 | 2218 | 22402 | 0.0418 |
1000 | 999.71 | 91 | 3.74 | 41.1 | 2767 | 27922 | 0.0335 |
AAAC Conductor according to EN50183
Code Name | Calculated Cross Section |
No..Dia.of Wires | Overall Diameter | Weight | Rated Strength |
mm² | No./mm | mm | kg/km | kN | |
Box | 18.8 | 7/1.85 | 5.55 | 51.4 | 5.55 |
Acacia | 23.8 | 7/2.08 | 6.24 | 64.9 | 7.02 |
Almond | 30.1 | 7/2.34 | 7.02 | 82.2 | 8.88 |
Cedar | 35.5 | 7/2.54 | 7.62 | 96.8 | 10.46 |
Deodar | 42.2 | 7/2.77 | 8.31 | 115.2 | 12.44 |
Fir | 47.8 | 7/2.95 | 8.85 | 130.6 | 14.11 |
Hazel | 59.9 | 7/3.30 | 9.90 | 163.4 | 17.66 |
Pine | 71.6 | 7/3.61 | 10.8 | 195.6 | 21.14 |
Holly | 84.1 | 7/3.91 | 11.7 | 229.5 | 24.79 |
Willow | 89.7 | 7/4.04 | 12.1 | 245,0 | 26.47 |
Oak | 118.9 | 7/4.65 | 14.0 | 324.5 | 35.07 |
Mulberry | 150.9 | 19/3.18 | 15.9 | 414.3 | 44.52 |
Ash | 180.7 | 19/3.48 | 17.4 | 496.1 | 53.31 |
Elm | 211.0 | 19/3.76 | 18.8 | 579.2 | 62.24 |
Poplar | 239.4 | 37/2.87 | 20.1 | 659.4 | 70.61 |
Sycamore | 303.2 | 37/3.23 | 22.6 | 835.2 | 89.40 |
Upas | 362.1 | 37/3.53 | 24.7 | 997.5 | 106.82 |
Yew | 479.0 | 37/4.06 | 28.4 | 1319.6 | 141.31 |
Totara | 498.1 | 37/4.14 | 29.0 | 1372.1 | 146.93 |
Rubus | 586.9 | 61/3.50 | 31.5 | 1622.0 | 173.13 |
Sorbus | 659.4 | 61/3.71 | 33.4 | 1822.5 | 194.53 |
Araucaria | 821.1 | 61/4.14 | 37.3 | 2269.4 | 242.24 |
Redwood | 996.2 | 61/4.56 | 41.0 | 2753.2 | 293.88 |
AAAC Conductor according to IEC61089
Code Number | A2 Conductor | A3 Conductor | Max.D.C. Resistance of Conductor at 20ºC | ||||||||
Number of Wires | Diameter of Wires | Diameter of Conductor | Approx. Weight | Rated Strength | Number of Wires | Diameter of Wires | Diameter of Conductor | Approx. Weight | Rated Strength | ||
mm² | – | mm | mm | kg/km | daN | – | mm | mm | kg/km | daN | Ω/km |
16 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 7 | 1.84 | 5.52 | 50.8 | 6.04 | 1.7896 |
25 | 7 | 2.29 | 6.87 | 78.7 | 8.49 | 7 | 2.30 | 6.9 | 79.5 | 9.44 | 1.1453 |
40 | 7 | 2.89 | 8.67 | 125.9 | 13.58 | 7 | 2.91 | 8.73 | 127.1 | 15.1 | 0.7158 |
63 | 7 | 3.63 | 10.8 | 198.3 | 21.39 | 7 | 3.65 | 10.95 | 200.2 | 23.06 | 0.4545 |
100 | 19 | 2.78 | 13.9 | 316.3 | 33.95 | 19 | 2.79 | 13.95 | 319.3 | 37.76 | 0.2877 |
125 | 19 | 3.10 | 15.5 | 395.4 | 42.44 | 19 | 3.12 | 15.6 | 399.2 | 47.20 | 0.2302 |
160 | 19 | 3.51 | 17.55 | 506.1 | 54.32 | 19 | 3.53 | 17.65 | 511.0 | 58.56 | 0.1798 |
200 | 19 | 3.93 | 19.65 | 623.7 | 67.91 | 19 | 3.95 | 19.75 | 638.7 | 73.20 | 0.1439 |
250 | 19 | 4.39 | 21.95 | 790.8 | 84.68 | 19 | 4.41 | 22.05 | 798.4 | 91.50 | 0.1151 |
315 | 37 | 3.53 | 24.71 | 998.9 | 106.95 | 37 | 3.55 | 24.85 | 1008.4 | 115.29 | 0.0916 |
400 | 37 | 3.98 | 27.86 | 1268.4 | 135.81 | 37 | 4.0 | 28 | 1280.5 | 146.4o | 0.0721 |
450 | 37 | 4.22 | 29.54 | 1426.9 | 152.79 | 37 | 4.24 | 29.68 | 1440.5 | 164.70 | 0.0641 |
500 | 37 | 4.45 | 31.15 | 1585.5 | 169.76 | 37 | 4.47 | 31.29 | 1600.6 | 183.oo | 0.0577 |
560 | 61 | 3.67 | 33.03 | 1778.4 | 190.14 | 61 | 3.69 | 33.21 | 1795.3 | 204.95 | 0.0516 |
630 | 61 | 3.89 | 35.01 | 2000.7 | 213.90 | 61 | 3.91 | 35.19 | 2019.8 | 230.58 | 0.0458 |
710 | 61 | 4.13 | 37.17 | 2254.8 | 241.07 | 61 | 4.15 | 37.35 | 2276.2 | 259.86 | 0.0407 |
800 | 61 | 4.38 | 39.42 | 2540.6 | 271.62 | 61 | 4.4 | 39.6 | 2564.8 | 282.80 | 0.0361 |
900 | 91 | 3.81 | 41.91 | 2861.1 | 305.58 | 91 | 3.83 | 42.13 | 2888.3 | 329.40 | 0.0321 |
1000 | 91 | 4.01 | 44.11 | 3179.0 | 339.53 | 91 | 4.03 | 44.33 | 3209.3 | 366.00 | 0.0289 |
1120 | 91 | 4.25 | 46.75 | 3560.5 | 380.27 | 91 | 4.27 | 46.97 | 3594.4 | 409.92 | 0 0258 |
1250 | 91 | 4.49 | 49.39 | 3973.7 | 424.41 | – | – | – | – |
4. Package
Packaged by standard wooden drum, steel-wooden drum, and steel drum.
We are China Aluminum Alloy AAAC Conductor AAAC 35mm2 manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAAC 35mm2"/> <meta name="Description" content="Aluminum Alloy AAAC Conductor AAAC 35mm2 Products
Popular Find Details and Price about AAAC 35mm2 from Aluminum Alloy AAAC Conductor AAAC 35mm2 - YIFANG ELECTRIC GROUP INC. Products
Popular YIFANG ELECTRIC GROUP INC. Products
Conductores De Aleacion De Aluminio AAAC Alton ASTM B398, 399
All Aluminum Alloy Conductor 288mm2
AAC/AAAC/ACSR Conductor Bare Conductor Overhead Conductor
3.8/6.6 (7.2) Kv U/G Cables 6.6kv, XLPE, 3X185mm2 Copper Conductor BS-6622 IEC 60502
33 Kv Ht Cable Unarmored 3X185mmsq Cu
Copper Conductor PVC Insulation Single Core Electric Wires 1.0, 1.5, 2.5, 4, 6mm2