Rh5z1-Ol 19/33kv Medium Voltage Cables

Rh5z1-Ol 19/33kv Medium Voltage Cables image
Get Latest Price Request a quote
You May Like
Product Details
Product Description
RH5Z1-OL-AL Cable WB-AL/XLPE/WBT/CWS/AL-PET/DMZ1 18/30kV
Reference standard
This type of cables is designed, manufactured and tested according to below standards:
IEC 60502-2, HD 620 10E-6
Halogen Free- IEC 60754-1/2,
Water resistance:AD8
UV Resistant: UNE 211605, HD 605, Subclause 2.2.13
This standard specifies the construction, dimensions and test requirements that must be accomplished by medium voltage cables with rated voltage Uo/U (Umax) = 8,7/15(17,5) kV, 12/20(24) kV, 15/25 (31) kV, 18/30(36) kV and 20/34,5(37,95) kV to be used in distribution systems.
CONSTRUCTION
RH5Z1(2OL) Cable Construction
Similar to the RHZ1 Cables, the RH5Z1 range has cross-linked Polyethylene (XLPE) insulation, a halogen-free Polyolefin outer sheath, waterblocking tape over the conductor and longitudinal waterblocking measures (RH5Z1-OL & RH5Z1-2OL).
The specification differs (‘H5’) with an Aluminium tape applied just below the outer sheath, which provides the dual function of moisture blocking and protective screening.
R | XLPE (Cross-linked Polyethylene) Insulation |
H5 | Metallic screen Aluminium |
Z1 | Polyolefin compound |
OL | Longitudinal watertightness over the insulation screen only |
2OL | Longitudinal watertightness in conductor and over insulation screen |
RH5Z1 Cable Sheath Material
As is the case with the RHZ1 cables, the Polyolefin sheathing material on the RH5Z1-OL & RH5Z1-2OL cables is a Polyethylene compound (PO DMZ1) – naturally halogen free, but not ‘Low Smoke Zero Halogen‘. It is compliant with IEC 60754-1/2. Where required, it can also be produced to be flame retardant (using PO compound DMZ2) to IEC 60332-1-2 and compliant to CPR Euroclassification Eca (S) and also flame retardant and compliant with CPR Euroclassification Cca s1b, d2, a2 (AS).
Cable Drawing and Cable Photo
Medium voltage aluminium cable with XLPE insulation and halogen free outer sheath.Suitable for power distribution in multiple applications including renewable energy installations.External use or direct burial.
Dimension and Current
No. of cores & CSA | Max. DC. Resistance of conductor at 20 ºC | Max. AC. Resistance of conductor at 90 ºC | Fault current capacity of conductor (1s) | Conductor to screen capacitance | Inductance | Max. allowable pulling force of conductor | Min. bending radius | |
During installation | After installation | |||||||
mm2 | Q/km | Q/km | kA | ^F/km | mH/km | kN | mm | mm |
1C630 | 0.0469 | 0.0624 | 59.52 | 0.372 | 0.325 | 24.6 | 1190 | 900 |
1C400 | 0.0778 | 0.101 | 37.79 | 0.297 | 0.345 | 15.6 | 1030 | 770 |
1C240 | 0.125 | 0.161 | 22.68 | 0.250 | 0.372 | 9.4 | 930 | 700 |
1C150 | 0.206 | 0.265 | 14.17 | 0.211 | 0.401 | 5.9 | 840 | 630 |
single-core cable with minimum fire reaction Eca are available too.