THW-Copper Conductor-PVC Insulation-Heat and Moisture Resistant-FlameRetardant
Application
THW conductors are primarily used in conduit or recognized raceways for services, feeders, and branch circuit wiring as specified in the National Electrical Code. THW conductors may be used in wet or dry locations at temperatures not to exceed 90°C dry or 75°C wet. Voltage rating for THW conductors is 600 volts. This product in sizes 500kcmil and larger is designed to be installed without the application of pulling lubricant.
Standards
• UL Standard 83
• NFPA 70; National Electrical Code® (NEC®);• ASTM B800, ASTM B801
• Flame Test FT-2, VW-1
Construction
THW Technical data
THW-2-Copper Conductor-PVC Insulation-Heat and Moisture Resistant-Flame Retardant 600V
Application
THW-2 conductors are primarily used in conduit or recognized raceways for services, feeders, and
branch circuitwiring as specified in the National Electrical Code. THW-2 conductors may be used
in wet or dry locations at temperatures not to exceed 90°C dry or 90°C wet. Voltage rating for THW-2 conductors is 600 volts. This product in sizes 500kcmil and larger is designed to be installed without the application of pulling lubricant.
Standards
• UL Standard 83
• NFPA 70; National Electrical Code® (NEC®);• ASTM B800, ASTM B801
• Flame Test FT-2, VW-1
THHN-Copper Conductor-PVC Insulation-Nylon Jacket-Heat and Moisture Resistant-Flame Retardant 600V
THHN Copper Conductor-PVC Insulation-Nylon Jacket Heat
Resistant and Flame Retardant 600V
Temperature rating not to exceed:
THHN/THWN: 90°C dry and dump, 600V
THHN/THWN: 75 °C wet or in oil, 600V
THWN-2: 90°C Dry, wet or in oil,600V
Application
Type THHN conductors are primarily used in conduit and cable trays for services, feeders, and branch circuits in commercial or industrial applications as specified in the National Electrical Code.the conductor
Standards
UL Standard 83
Voltage rating
600V
Flame test marking
FT1/VW-1
Conductor | Insulation | Nylon | O.D. (mm) |
Approximate weight kg/km | (20OC) Max. conductor dc resista nee Q/km |
Allowable Ampacities 90C (A) |
||
America Wire (AWG) |
No. of wire conductor (No.) |
O.D. (mm) |
Thick ness (mm) |
Thick ness (mm) |
||||
14AWG | 7 | 1.80 | 0.38 | 0.10 | 2.9 | 24.9 | 8.62 | 15 |
12AWG | 7 | 2.26 | 0.38 | 0.10 | 3.4 | 37.2 | 5.43 | 20 |
10AWG | 7 | 2.87 | 0.51 | 0.10 | 4.3 | 59.0 | 3.41 | 30 |
8AWG | 7 | 3.6 | 0.76 | 0.13 | 5.7 | 97.2 | 2.14 | 55 |
6AWG | 7 | 4.5 | 0.76 | 0.13 | 6.6 | 145.5 | 1.35 | 75 |
4AWG | 7 | 5.6 | 1.02 | 0.15 | 8.3 | 233.0 | 0.848 | 100 |
3AWG | 7 | 6.3 | 1.02 | 0.15 | 9.0 | 286.4 | 0.673 | 115 |
2AWG | 7 | 7.2 | 1.02 | 0.15 | 9.9 | 353.6 | 0.534 | 130 |
1AWG | 19 | 8.2 | 1.27 | 0.18 | 11.6 | 455.4 | 0.423 | 145 |
1/0AWG | 19 | 9.2 | 1.27 | 0.18 | 12.6 | 562.0 | 0.335 | 170 |
2/0AWG | 19 | 10.0 | 1.27 | 0.18 | 13.5 | 692.0 | 0.266 | 195 |
3/0AWG | 19 | 11.6 | 1.27 | 0.18 | 15.1 | 861.3 | 0.211 | 225 |
4/0AWG | 19 | 13.0 | 1.27 | 0.18 | 16.5 | 1068.1 | 0.167 | 260 |
250kcmil | 37 | 14.2 | 1.52 | 0.20 | 18.3 | 1281.2 | 0.142 | 290 |
300kcmil | 37 | 15.4 | 1.52 | 0.20 | 19.5 | 1514.8 | 0.118 | 320 |
350kcmil | 37 | 17.0 | 1.52 | 0.20 | 21.2 | 1752.2 | 0.101 | 350 |
400kcmil | 37 | 18.0 | 1.52 | 0.20 | 22.2 | 1992.8 | 0.0885 | 380 |
500Kcmil | 37 | 20.0 | 1.52 | 0.20 | 24.2 | 2456.3 | 0.0709 | 430 |
600Kcmil | 61 | 22.0 | 1.78 | 0.23 | 26.9 | 2970.0 | 0.0590 | 475 |
750Kcmil | 61 | 24.4 | 1.78 | 0.23 | 29.4 | 3672.2 | 0.0472 | 535 |
1000Kcmil | 61 | 28.4 | 1.78 | 0.23 | 33.5 | 4845.5 | 0.0354 | 615 |
Cable structure
Conductor
ClassCopper Conductor
Insulation
(PVC)
sheath
Nylon Jacket
THWN-Copper Conductor-PVC Insulation-Nylon Jacket Heat and Moisture
Resistant-Flame Retardant 600V
Application
THWN conductors are primarily used in conduit or recognized raceways for services, feeders, and branch circuit wiring as specified in the National Electrical Code.
THWN conductors may be used in wet or dry locations at temperatures not to exceed
75°C dry and wet. Voltage rating for THWN conductors is 600 volts. This product in
sizes 500kcmil and larger is designed to be installed without the application of pulling
lubricant.
Standards
• UL Standard 83
• NFPA 70; National Electrical Code® (NEC®);• ASTM B800, ASTM B801
• Flame Test FT-2, VW-1
- Imported equipment with experienced technical team
The company have three plant and has 3048 employees which have 206 engineers. Plant has a series of imported production lines including Niehoff copper drawing lines, Troster Germany and Maillefer Finland 500KV VCV lines, stranding machine from Pourtier France, SKET Germany, Caballe Spain, 220KV and 35KV production line plus SIKORA X – RAY 8000 on-line eccentricity measuring unit from Germany - Complete certification system
Qifan Cable have gotten ISO 9001, ISO 14001, OHSAS 18001. Plant passed TUV, VDE, UL, CE, SAA, BS etc. certificate. - Perfect Production system
Qifan Cable products cover LV power cable, MV power cable, HV&EHV power cable, ABC cables, ACSR/AAC/AAAC/ACAR/OPGW ,submarine cable, control cable, instrumentation cable, building wire, flexible rubber cable, fire rated cable, renewable cable, solar cable, industrial cable, Lan cable, coaxial cable etc. - Perfect Sales service system
Qifan Cable can offer the OEM/ODM service, Multiple products, Skilled Export sale engineer team, Reasonable price, Reliable quality, Friendly service. Qifan is always your best choice.
We are China Copper Conductor-PVC Insulation-Heat and Moisture Resistant-Flame Retardant Thw manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Tags: Ltd., Shanghai QIFAN Cable Co., Thw, Thw Cable