N2XS2Y Cross-Linked Polyethylene Insulation Medium voltage power cables
APPLICATION
Voltage Rating Uo/U (Um)
6/10 (12)kV
Temperature Rating
Maximum conductor operating temperature:90°C
Initial temperature at S.C.C for metallic screen:80°C
Maximum conductor temperature during S.C: 250°C
Minimum Bending Radius
20 x overall diameter
STANDARDS
IEC 60502-2, IEC 60228
Class 2 Stranded Copper
Conductor Screen
Semi-conductive material (Bonded type)
Insulation
XLPE (Cross-Linked Polyethylene)
Insulation Screen
Semi-conductive material (Strippabe type)
Screen
Copper wires with Open Helix Copper Tape Screen
Outer Sheath
MDPE (Medium Density Polyethylene
DIMENSIONS 6/10KV | ||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL SCREEN CROSS SECTIONAL AREA mm2 |
NOMINAL INSULATION THICKNESS mm |
NOMINAL SHEATH THICKNESS mm |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
1 | 50 | 16 | 3.4 | 1.7 | 21.8 | 840 |
1 | 70 | 16.08 | 3.4 | 1.7 | 23.6 | 1055 |
1 | 95 | 16.08 | 3.4 | 1.8 | 25.1 | 1316 |
1 | 120 | 16.08 | 3.4 | 1.8 | 26.5 | 1561 |
1 | 150 | 25.37 | 3.4 | 1.9 | 28.5 | 1934 |
1 | 185 | 25.37 | 3.4 | 1.9 | 30 | 2270 |
1 | 240 | 25.37 | 3.4 | 2 | 32.6 | 2847 |
1 | 300 | 25.37 | 3.4 | 2.1 | 35 | 3408 |
1 | 400 | 35.47 | 3.4 | 2.2 | 38 | 4320 |
1 | 500 | 35.47 | 3.4 | 2.3 | 41.6 | 5307 |
1 | 630 | 35.47 | 3.4 | 2.4 | 46.5 | 6716 |
1 | 800 | 35.47 | 3.4 | 2.5 | 50.8 | 8490 |
N2XS2Y XLPE MDPE 8.7/15 (17.5) kV Cable | ||||||
DIMENSIONS | ||||||
NO. OF CORE |
NOMINAL CROSS SECTIONAL AREA |
NOMINAL SCREEN CROSS SECTIONAL AREA |
NOMINAL INSULATION THICKNESS |
NOMINAL SHEATH THICKNESS |
NOMINAL OVERALL DIAMTER |
NOMINAL WEIGHT |
mm2 | mm2 | mm | mm | mm | kg/km | |
1 | 50 | 16 | 4.5 | 1.7 | 23.80 | 904 |
1 | 70 | 16 | 4.5 | 1.8 | 25.80 | 1132 |
1 | 95 | 16 | 4.5 | 1.8 | 27.10 | 1389 |
1 | 120 | 16 | 4.5 | 1.9 | 28.70 | 1647 |
1 | 150 | 25 | 4.5 | 2 | 30.70 | 2027 |
1 | 185 | 25 | 4.5 | 2 | 32.20 | 2368 |
1 | 240 | 25 | 4.5 | 2.1 | 34.60 | 2943 |
1 | 300 | 25 | 4.5 | 2.2 | 37.20 | 3522 |
1 | 400 | 35 | 4.5 | 2.3 | 40.20 | 4445 |
1 | 500 | 35 | 4.5 | 2.4 | 43.80 | 5444 |
1 | 630 | 35 | 4.5 | 2.5 | 48.70 | 6869 |
1 | 800 | 35 | 4.5 | 2.6 | 53 | 8655 |
DIMENSIONS 12/20KV | ||||||
NO.OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL SCREEN CROSS SECTIONAL AREA mm2 |
NOMINAL INSULATION THICKNESS mm |
NOMINAL SHEATH THICKNESS mm |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
1 | 50 | 16 | 5.5 | 1.8 | 26 | 982 |
1 | 70 | 16 | 5.5 | 1.9 | 28 | 1217 |
1 | 95 | 16 | 5.5 | 1.9 | 29.3 | 1478 |
1 | 120 | 16 | 5.5 | 2 | 30.9 | 1741 |
1 | 150 | 25 | 5.5 | 2 | 32.7 | 2116 |
1 | 185 | 25 | 5.5 | 2.1 | 34.2 | 2462 |
1 | 240 | 25 | 5.5 | 2.2 | 36.8 | 3056 |
1 | 300 | 25 | 5.5 | 2.2 | 39.2 | 3630 |
1 | 400 | 35 | 5.5 | 2.3 | 42.2 | 4562 |
1 | 500 | 35 | 5.5 | 2.4 | 45.8 | 5573 |
1 | 630 | 35 | 5.5 | 2.5 | 50.7 | 7011 |
1 | 800 | 35 | 5.5 | 2.7 | 55.2 | 8829 |
N2XS2Y 18/30 (36)kV Cable | ||||||
DIMENSIONS | ||||||
NO. OF CORE |
NOMINAL CROSS SECTIONAL AREA |
NOMINAL SCREEN CROSS SECTIONAL AREA |
NOMINAL INSULATION THICKNESS |
NOMINAL SHEATH THICKNESS |
NOMINAL OVERALL DIAMTER |
NOMINAL WEIGHT |
mm2 | mm2 | mm | mm | mm | kg/km | |
1 | 50 | 16 | 8 | 2 | 31.4 | 1203 |
1 | 70 | 16 | 8 | 2 | 33.2 | 1443 |
1 | 95 | 16 | 8 | 2.1 | 34.5 | 1715 |
1 | 120 | 16 | 8 | 2.1 | 35.9 | 1979 |
1 | 150 | 25 | 8 | 2.2 | 37.9 | 2377 |
1 | 185 | 25 | 8 | 2.2 | 39.4 | 2735 |
1 | 240 | 25 | 8 | 2.3 | 42.0 | 3349 |
1 | 300 | 25 | 8 | 2.4 | 44.6 | 3958 |
1 | 400 | 35 | 8 | 2.5 | 47.6 | 4914 |
1 | 500 | 35 | 8 | 2.6 | 51.2 | 5952 |
1 | 630 | 35 | 8 | 2.7 | 56.1 | 7429 |
1 | 800 | 35 | 8 | 2.8 | 60.4 | 9265 |
THE CABLE TEST
We have world-class testing facility, and made rigorous testing regime, every meter of cable before leaving the factory must go through strict testing, testing qualified products will be shipped to customers, effectively ensure product quality and meet customer requirements.
SUSTAINABILITY COMMITMENT
Guowang Cable actively implements the “carbon reduction” goal, strives to promote the green’s low-carbon transformation,strengthens energy-saving and emission reduction technology innovation, and promotes the company’s healthy and sustain-able development.
We are China N2xs2y Cross-Linked Polyethylene Insulation Medium Voltage Power Cables manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Tags: Henan Guowang Cable Group Co., Ltd., N2xs2y 12kv, N2xs2y 6 10 Kv