5KV to 46KV Medium Voltage Cable
Application: Medium voltage power cables are apply for power transmission and distribution line at AC rated voltage up to 46kV.
Applicable standards: IEC60502-2, BS6622, SANS1339, AS/NZS1429.1, DIN VDE 0276-626, NFC 33-226, IEC60840, ICEA S-93-639,ICEA S-94-649, HD620,CSA C68.10or the standards agreed by both of the customers and us.
Construction:
Conductor: IEC60228 class 1 class 2 bear copper/Aluminum etc
Conductor Screen: Semi-conducting compound
Insulation: XLPE or EPR
Insulation Screen: Semi-conducting compound
Core: 1core or 3cores
Shield: Copper wire/ Copper tape/AL plastic tape/Aluminum tape
Inner Sheath( optional): PVC PE LSZH CPE
Armoured ( optional): Galvanized steel wire/Aluminum wire/Two layers of Aluminum tapegap-wrapped /Two layers of steel tape gap-wrapped / Galvanized steel interlocked armour/Aluminum alloy interlocked armour
Outer Sheath: PVC PE LSZH CPE
3.6/6KV XLPE Insulated aluminum wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
1×25 | 2.5 | 23.8 | 866 | 715 | 0.727 | 1.20 | 140 | 163 | 108 | 127 |
1×35 | 2.5 | 24.9 | 993 | 784 | 0.524 | 0.868 | 166 | 198 | 129 | 154 |
1×50 | 2.5 | 26.0 | 1152 | 867 | 0.387 | 0.641 | 196 | 238 | 152 | 184 |
1×70 | 2.5 | 27.7 | 1407 | 994 | 0.268 | 0.443 | 239 | 296 | 186 | 230 |
1×95 | 2.5 | 29.6 | 1721 | 1152 | 0.193 | 0.320 | 285 | 361 | 221 | 280 |
1×120 | 2.5 | 31.1 | 1994 | 1275 | 0.153 | 0.253 | 323 | 417 | 252 | 324 |
1×150 | 2.5 | 32.7 | 2301 | 1425 | 0.124 | 0.206 | 361 | 473 | 281 | 368 |
1×185 | 2.5 | 35.4 | 2804 | 1696 | 0.0991 | 0.164 | 406 | 543 | 317 | 424 |
1×240 | 2.6 | 38.0 | 3430 | 1976 | 0.0754 | 0.125 | 469 | 641 | 367 | 502 |
1×300 | 2.8 | 40.8 | 4119 | 2294 | 0.0601 | 0.100 | 526 | 735 | 414 | 577 |
1×400 | 3.0 | 44.4 | 5043 | 2706 | 0.0470 | 0.0778 | 590 | 845 | 470 | 673 |
1×500 | 3.2 | 49.8 | 6393 | 3398 | 0.0366 | 0.0605 | 735 | 958 | 578 | 767 |
1×630 | 3.2 | 53.9 | 7892 | 4024 | 0.0283 | 0.0469 | 831 | 1098 | 665 | 896 |
1×800 | 3.2 | 58.2 | 9719 | 4757 | 0.0221 | 0.0367 | 945 | 1266 | 761 | 1041 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
3.6/6KV XLPE Insulated steel wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Nominal Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
3×25 | 2.5 | 41.9 | 3207 | 2748 | 0.727 | 1.20 | 129 | 143 | 100 | 111 |
3×35 | 2.5 | 45.6 | 4054 | 3430 | 0.524 | 0.868 | 154 | 172 | 119 | 133 |
3×50 | 2.5 | 48.2 | 4654 | 3792 | 0.387 | 0.641 | 181 | 205 | 140 | 159 |
3×70 | 2.5 | 52.2 | 5592 | 4347 | 0.268 | 0.443 | 220 | 253 | 171 | 196 |
3×95 | 2.5 | 56.1 | 6703 | 4975 | 0.193 | 0.320 | 263 | 307 | 204 | 238 |
3×120 | 2.5 | 60.0 | 7762 | 5582 | 0.153 | 0.253 | 298 | 352 | 232 | 274 |
3×150 | 2.5 | 63.4 | 8878 | 6187 | 0.124 | 0.206 | 332 | 397 | 259 | 309 |
3×185 | 2.5 | 67.3 | 10248 | 6881 | 0.0991 | 0.164 | 374 | 453 | 293 | 354 |
3×240 | 2.6 | 73.5 | 12509 | 8072 | 0.0754 | 0.125 | 431 | 529 | 338 | 415 |
3×300 | 2.8 | 81.0 | 15741 | 10190 | 0.0601 | 0.100 | 482 | 599 | 380 | 472 |
3×400 | 3.0 | 88.8 | 19093 | 11996 | 0.0470 | 0.0778 | 541 | 683 | 432 | 545 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
18/30KV XLPE Insulated aluminum wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
1×35 | 8.0 | 37.4 | 1840 | 1630 | 0.524 | 0.868 | 170 | 201 | 132 | 158 |
1×50 | 8.0 | 38.7 | 2036 | 1751 | 0.387 | 0.641 | 200 | 242 | 156 | 190 |
1×70 | 8.0 | 40.4 | 2335 | 1920 | 0.268 | 0.443 | 242 | 300 | 190 | 235 |
1×95 | 8.0 | 42.3 | 2681 | 2112 | 0.193 | 0.320 | 288 | 363 | 224 | 285 |
1×120 | 8.0 | 43.8 | 2996 | 2278 | 0.153 | 0.253 | 326 | 420 | 256 | 328 |
1×150 | 8.0 | 46.4 | 3506 | 2621 | 0.124 | 0.206 | 364 | 476 | 286 | 372 |
1×185 | 8.0 | 48.3 | 3970 | 2862 | 0.0991 | 0.164 | 409 | 546 | 321 | 428 |
1×240 | 8.0 | 50.9 | 4661 | 3207 | 0.0754 | 0.125 | 472 | 645 | 372 | 505 |
1×300 | 8.0 | 53.5 | 5380 | 3555 | 0.0601 | 0.100 | 529 | 740 | 418 | 578 |
1×400 | 8.0 | 56.7 | 6333 | 3996 | 0.0470 | 0.0778 | 593 | 848 | 475 | 675 |
1×500 | 8.0 | 60.5 | 7556 | 4561 | 0.0366 | 0.0605 | 740 | 963 | 583 | 772 |
1×630 | 8.0 | 64.8 | 9172 | 5304 | 0.0283 | 0.0469 | 835 | 1101 | 675 | 900 |
1×800 | 8.0 | 69.1 | 11063 | 6101 | 0.0221 | 0.0367 | 950 | 1272 | 765 | 1046 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
18/30KV XLPE Insulated steel wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
3×35 | 8.0 | 72.1 | 7473 | 6848 | 0.524 | 0.868 | 154 | 175 | 118 | 132 |
3×50 | 8.0 | 76.2 | 9011 | 8149 | 0.387 | 0.641 | 180 | 210 | 139 | 158 |
3×70 | 8.0 | 80.3 | 10196 | 8951 | 0.268 | 0.443 | 217 | 258 | 171 | 200 |
3×95 | 8.0 | 84.4 | 11479 | 9751 | 0.193 | 0.320 | 261 | 310 | 204 | 240 |
3×120 | 8.0 | 88.0 | 12743 | 10563 | 0.153 | 0.253 | 296 | 353 | 229 | 279 |
3×150 | 8.0 | 91.2 | 13918 | 11228 | 0.124 | 0.206 | 332 | 405 | 256 | 310 |
3×185 | 8.0 | 95.3 | 15562 | 12196 | 0.0991 | 0.164 | 374 | 458 | 293 | 360 |
3×240 | 8.0 | 101.1 | 18038 | 13601 | 0.0754 | 0.125 | 429 | 535 | 338 | 420 |
3×300 | 8.0 | 106.2 | 20502 | 14952 | 0.0601 | 0.100 | 482 | 602 | 380 | 474 |
3×400 | 8.0 | 113.0 | 23898 | 16800 | 0.0470 | 0.0778 | 541 | 690 | 428 | 545 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
Products Pictures
Packing and loading containers pictures:
* We can design and produce ACSR according to client’s requirement. Any requirement, feel free to contact us!
Company Information
Certification
FAQ
1. Q:How does your factory control the quality?
A:Factory has a quick and enthusiastic merchandisers team, strict and responsible QC team, service for many well-known brands all around the world with our high-quality products and strict.
2. Q:Can I visit your company?
A: Sure,If you need,we will arrange the driver to pick you up.
3. Q:How can I get some samples?
A: Contact me on below,Determin sample and address for shipping.
4. Q:Have you ever supplied cables to our country?
A: Henway Cables have been sold to over 100 countries and regions in the world. you can contact me for details.
5. Q:What is your MOQ?
A: MOQ Normally 500 meters for big diameter cables. Please contact me for detail info if you have specific cable requirement.
6. Q:When can I get the price?
A: Usually quote within 6 hours after we get your inquiry.
7. Q:How long is your delivery time?
A: According to your order’s quantity. Usually our lead time is 3 – 20 working days.
For more information about wires and cables, please feel free to contact us. Your inquiries will be replied to within 6 hours!!
We are China Medium Voltage 6/10 (12) Kv Cu/XLPE/Cws+Cts/PVC N2xsh Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 24kv Power Cable Products
5kv-35kv Medium Voltage Copper/Aluminum Conductor XLPE Insulation Power Cables
European Medium Voltage Power Cable N2xsy 6/10kv 12/20kv 18/30kv
3 Core Copper Conductor Medium Voltage Armoured XLPE Insulated Power Cable
Popular 3X240 Cable Products
Popular Henway Electric Group Inc Products
Ad8 Solar Cable Fire Rating Low Smoke Halogen-Free 4mm2
11kv Medium Voltage XLPE Insulated Yjlv 1*500 PVC Sheath Power Cable
Factory Price Flame Retardant Low Voltage XLPE Insulated Unarmoured Power Cable
High Quality Tinned Copper Double Core Solar Cable 2X4mm2 Electric Wire Cable
Yjv Yjlv Yjv22 Yjv32 Yjlv 22 Yjlv32 Medium Voltage Cu/Al Conductor Armoured Power Cable
Popular Products
3 Core Copper Conductor Medium Voltage Armoured XLPE Insulated Power Cable
European Medium Voltage Power Cable N2xsy 6/10kv 12/20kv 18/30kv
5kv-35kv Medium Voltage Copper/Aluminum Conductor XLPE Insulation Power Cables
Tags: 24kv Power Cable, 3X240 Cable, Henway Electric Group Inc