Product Description
5KV to 46KV Medium Voltage Cable
Application: Medium voltage power cables are apply for power transmission and distribution line at AC rated voltage up to 46kV.
Applicable standards: IEC60502-2, BS6622, SANS1339, AS/NZS1429.1, DIN VDE 0276-626, NFC 33-226, IEC60840, ICEA S-93-639,ICEA S-94-649, HD620,CSA C68.10or the standards agreed by both of the customers and us.
Construction:
Conductor: IEC60228 class 1 class 2 bear copper/Aluminum etc
Conductor Screen: Semi-conducting compound
Insulation: XLPE or EPR
Insulation Screen: Semi-conducting compound
Core: 1core or 3cores
Shield: Copper wire/ Copper tape/AL plastic tape/Aluminum tape
Inner Sheath( optional): PVC PE LSZH CPE
Armoured ( optional): Galvanized steel wire/Aluminum wire/Two layers of Aluminum tapegap-wrapped /Two layers of steel tape gap-wrapped / Galvanized steel interlocked armour/Aluminum alloy interlocked armour
Outer Sheath: PVC PE LSZH CPE
3.6/6KV XLPE Insulated aluminum wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
1×25 | 2.5 | 23.8 | 866 | 715 | 0.727 | 1.20 | 140 | 163 | 108 | 127 |
1×35 | 2.5 | 24.9 | 993 | 784 | 0.524 | 0.868 | 166 | 198 | 129 | 154 |
1×50 | 2.5 | 26.0 | 1152 | 867 | 0.387 | 0.641 | 196 | 238 | 152 | 184 |
1×70 | 2.5 | 27.7 | 1407 | 994 | 0.268 | 0.443 | 239 | 296 | 186 | 230 |
1×95 | 2.5 | 29.6 | 1721 | 1152 | 0.193 | 0.320 | 285 | 361 | 221 | 280 |
1×120 | 2.5 | 31.1 | 1994 | 1275 | 0.153 | 0.253 | 323 | 417 | 252 | 324 |
1×150 | 2.5 | 32.7 | 2301 | 1425 | 0.124 | 0.206 | 361 | 473 | 281 | 368 |
1×185 | 2.5 | 35.4 | 2804 | 1696 | 0.0991 | 0.164 | 406 | 543 | 317 | 424 |
1×240 | 2.6 | 38.0 | 3430 | 1976 | 0.0754 | 0.125 | 469 | 641 | 367 | 502 |
1×300 | 2.8 | 40.8 | 4119 | 2294 | 0.0601 | 0.100 | 526 | 735 | 414 | 577 |
1×400 | 3.0 | 44.4 | 5043 | 2706 | 0.0470 | 0.0778 | 590 | 845 | 470 | 673 |
1×500 | 3.2 | 49.8 | 6393 | 3398 | 0.0366 | 0.0605 | 735 | 958 | 578 | 767 |
1×630 | 3.2 | 53.9 | 7892 | 4024 | 0.0283 | 0.0469 | 831 | 1098 | 665 | 896 |
1×800 | 3.2 | 58.2 | 9719 | 4757 | 0.0221 | 0.0367 | 945 | 1266 | 761 | 1041 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
3.6/6KV XLPE Insulated steel wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Nominal Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
3×25 | 2.5 | 41.9 | 3207 | 2748 | 0.727 | 1.20 | 129 | 143 | 100 | 111 |
3×35 | 2.5 | 45.6 | 4054 | 3430 | 0.524 | 0.868 | 154 | 172 | 119 | 133 |
3×50 | 2.5 | 48.2 | 4654 | 3792 | 0.387 | 0.641 | 181 | 205 | 140 | 159 |
3×70 | 2.5 | 52.2 | 5592 | 4347 | 0.268 | 0.443 | 220 | 253 | 171 | 196 |
3×95 | 2.5 | 56.1 | 6703 | 4975 | 0.193 | 0.320 | 263 | 307 | 204 | 238 |
3×120 | 2.5 | 60.0 | 7762 | 5582 | 0.153 | 0.253 | 298 | 352 | 232 | 274 |
3×150 | 2.5 | 63.4 | 8878 | 6187 | 0.124 | 0.206 | 332 | 397 | 259 | 309 |
3×185 | 2.5 | 67.3 | 10248 | 6881 | 0.0991 | 0.164 | 374 | 453 | 293 | 354 |
3×240 | 2.6 | 73.5 | 12509 | 8072 | 0.0754 | 0.125 | 431 | 529 | 338 | 415 |
3×300 | 2.8 | 81.0 | 15741 | 10190 | 0.0601 | 0.100 | 482 | 599 | 380 | 472 |
3×400 | 3.0 | 88.8 | 19093 | 11996 | 0.0470 | 0.0778 | 541 | 683 | 432 | 545 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
18/30KV XLPE Insulated aluminum wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
1×35 | 8.0 | 37.4 | 1840 | 1630 | 0.524 | 0.868 | 170 | 201 | 132 | 158 |
1×50 | 8.0 | 38.7 | 2036 | 1751 | 0.387 | 0.641 | 200 | 242 | 156 | 190 |
1×70 | 8.0 | 40.4 | 2335 | 1920 | 0.268 | 0.443 | 242 | 300 | 190 | 235 |
1×95 | 8.0 | 42.3 | 2681 | 2112 | 0.193 | 0.320 | 288 | 363 | 224 | 285 |
1×120 | 8.0 | 43.8 | 2996 | 2278 | 0.153 | 0.253 | 326 | 420 | 256 | 328 |
1×150 | 8.0 | 46.4 | 3506 | 2621 | 0.124 | 0.206 | 364 | 476 | 286 | 372 |
1×185 | 8.0 | 48.3 | 3970 | 2862 | 0.0991 | 0.164 | 409 | 546 | 321 | 428 |
1×240 | 8.0 | 50.9 | 4661 | 3207 | 0.0754 | 0.125 | 472 | 645 | 372 | 505 |
1×300 | 8.0 | 53.5 | 5380 | 3555 | 0.0601 | 0.100 | 529 | 740 | 418 | 578 |
1×400 | 8.0 | 56.7 | 6333 | 3996 | 0.0470 | 0.0778 | 593 | 848 | 475 | 675 |
1×500 | 8.0 | 60.5 | 7556 | 4561 | 0.0366 | 0.0605 | 740 | 963 | 583 | 772 |
1×630 | 8.0 | 64.8 | 9172 | 5304 | 0.0283 | 0.0469 | 835 | 1101 | 675 | 900 |
1×800 | 8.0 | 69.1 | 11063 | 6101 | 0.0221 | 0.0367 | 950 | 1272 | 765 | 1046 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
18/30KV XLPE Insulated steel wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
3×35 | 8.0 | 72.1 | 7473 | 6848 | 0.524 | 0.868 | 154 | 175 | 118 | 132 |
3×50 | 8.0 | 76.2 | 9011 | 8149 | 0.387 | 0.641 | 180 | 210 | 139 | 158 |
3×70 | 8.0 | 80.3 | 10196 | 8951 | 0.268 | 0.443 | 217 | 258 | 171 | 200 |
3×95 | 8.0 | 84.4 | 11479 | 9751 | 0.193 | 0.320 | 261 | 310 | 204 | 240 |
3×120 | 8.0 | 88.0 | 12743 | 10563 | 0.153 | 0.253 | 296 | 353 | 229 | 279 |
3×150 | 8.0 | 91.2 | 13918 | 11228 | 0.124 | 0.206 | 332 | 405 | 256 | 310 |
3×185 | 8.0 | 95.3 | 15562 | 12196 | 0.0991 | 0.164 | 374 | 458 | 293 | 360 |
3×240 | 8.0 | 101.1 | 18038 | 13601 | 0.0754 | 0.125 | 429 | 535 | 338 | 420 |
3×300 | 8.0 | 106.2 | 20502 | 14952 | 0.0601 | 0.100 | 482 | 602 | 380 | 474 |
3×400 | 8.0 | 113.0 | 23898 | 16800 | 0.0470 | 0.0778 | 541 | 690 | 428 | 545 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
Products Pictures
Packing and loading containers pictures:
* We can design and produce ACSR according to client’s requirement. Any requirement, feel free to contact us!
Company Information
Certification
FAQ
1. Q:How does your factory control the quality?
A:Factory has a quick and enthusiastic merchandisers team, strict and responsible QC team, service for many well-known brands all around the world with our high-quality products and strict.
2. Q:Can I visit your company?
A: Sure,If you need,we will arrange the driver to pick you up.
3. Q:How can I get some samples?
A: Contact me on below,Determin sample and address for shipping.
4. Q:Have you ever supplied cables to our country?
A: Henway Cables have been sold to over 100 countries and regions in the world. you can contact me for details.
5. Q:What is your MOQ?
A: MOQ Normally 500 meters for big diameter cables. Please contact me for detail info if you have specific cable requirement.
6. Q:When can I get the price?
A: Usually quote within 6 hours after we get your inquiry.
7. Q:How long is your delivery time?
A: According to your order’s quantity. Usually our lead time is 3 – 20 working days.
For more information about wires and cables, please feel free to contact us. Your inquiries will be replied to within 6 hours!!
We are China IEC60502 Low and Medium Voltage Aluminum Price Swa Electrical Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Henway Electric Group Inc Products
Underground Cu/XLPE/PVC/Swa/PVC Sheathed Low Voltage Power Cable in Nigeria
Medium Voltage Copper Conductor Steel Wire Armoured 3X150 Power Cable
Aluminum Core 1000V XLPE Insulation Interlocking Armored Wire 12-2 Mc Cable
Electric Build Cable Copper Conductor PVC Insulated Wire 2X1.5mm2 Nyify
Popular IEC60502 Products
Popular Medium Voltage Aluminum Cable Products
Popular Products
Solar Cable DC Cable (4mm2 6mm2 10mm2 2X6mm2 2X10mm2)
Flexible PVC Insulated and Sheathed 3 Core 1mm Control Cable
33kv PVC/XLPE/PE Insulated PVC Sheatd Aluminum Copper Under Armoured Medium Voltage Power Cable
Underground Aluminium Conductor 8.7/15kv 3X185mm2 Medium Voltage Power Cable Price
Tags: Henway Electric Group Inc, IEC60502, Medium Voltage Aluminum Cable