NFC33-226 is a medium voltage power cable with a rated voltage of 12kV to 20kV. The cables are available in single core or 3×1 construction and are suitable for buried, direct burial in soil or free air laying. The cable can be supplied with sheath colors according to the installation code: red for underground connections, gray for aerial, surface/underground and technical applications.
Specifically, product features and parameters of NFC33-226 cables may include:
1.Suitable for medium voltage power system from 12kV to 20kV;
2.Single core or 3×1 (clover) structure available;
3.It can be laid underground, directly buried in soil or in free air;
4.Sheath color can be selected according to installation specifications;
5.Aluminum material as a conductor;
6.XLPE and PE materials as insulation and sheath materials.
Features
- It can be applied to medium-voltage power systems from 12kV to 20kV, providing an efficient and reliable power transmission solution;
- Single core or 3×1 structure can be provided according to application requirements, which can meet the needs of different circuit connection methods;
- It can be laid underground, directly buried in soil or in free air, suitable for different application scenarios;
- Different colors of sheaths can be selected according to installation specifications, which helps to distinguish different types of cables and realize management and maintenance;
- Aluminum material is used as the conductor, which is not only light in weight and low in cost, but also has good electrical conductivity, thermal conductivity and corrosion resistance;
- XLPE and PE materials are used as insulation and sheath materials, which have good performances such as voltage resistance, heat resistance, and welding resistance.
Application
NFC33-226 cables are suitable for medium voltage power systems, with rated voltages between 12kV and 20kV. It can be used as a distribution line to transmit power, lighting and control signals, and can be applied in different scenarios, such as directly buried in the ground, laid in free air or buried in the soil.
More specifically, the application areas of NFC33-226 may include
1.Municipal engineering
Applied in the power distribution network of urban public facilities, streets and other areas
2.Industrial and mining enterprises:
Used in the construction and transformation of power distribution trunk lines in factories, mines and other places;
3.Residential quarters
Used as power distribution lines in residential quarters and villas.
Construction
Medium-voltage power cables have shielding and sheathing, and non-magnetic armoring can be used under necessary conditions. Refer to the figure below for the structure of conventional cables.
Performance
Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
3×1×50 | 3.4 | 23.1 | 53.4 | 2603 | 0.387 | 230 | 235 |
3×1×70 | 3.4 | 24.9 | 57.5 | 3316 | 0.268 | 285 | 295 |
3×1×95 | 3.4 | 26.6 | 61.2 | 4153 | 0.193 | 340 | 360 |
3×1×120 | 3.4 | 28.3 | 64.9 | 4953 | 0.153 | 385 | 420 |
3×1×150 | 3.4 | 29.9 | 67.9 | 5815 | 0.124 | 430 | 475 |
3×1×185 | 3.4 | 31.5 | 72.0 | 6947 | 0.0991 | 485 | 550 |
3×1×240 | 3.4 | 34.0 | 77.6 | 8704 | 0.0754 | 560 | 650 |
NFC 33-226 Medium voltage cables (non-aerial) 6/10kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
3×1×50 | 3.4 | 23.1 | 53.4 | 1739 | 0.641 | 180 | 185 |
3×1×70 | 3.4 | 24.9 | 57.5 | 2070 | 0.443 | 220 | 230 |
3×1×95 | 3.4 | 26.6 | 61.2 | 2420 | 0.320 | 260 | 280 |
3×1×120 | 3.4 | 28.3 | 64.9 | 2769 | 0.253 | 300 | 325 |
3×1×150 | 3.4 | 29.9 | 67.9 | 3115 | 0.206 | 335 | 370 |
3×1×185 | 3.4 | 31.5 | 72.0 | 3574 | 0.164 | 380 | 425 |
3×1×240 | 3.4 | 34.0 | 77.6 | 4267 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 6/10kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
3×1×50 | 4.5 | 25.5 | 58.6 | 2892 | 0.387 | 230 | 245 |
3×1×70 | 4.5 | 27.3 | 62.7 | 3626 | 0.268 | 280 | 305 |
3×1×95 | 4.5 | 29.0 | 66.4 | 4481 | 0.193 | 335 | 375 |
3×1×120 | 4.5 | 30.7 | 70.1 | 5299 | 0.153 | 385 | 425 |
3×1×150 | 4.5 | 32.3 | 73.1 | 6176 | 0.124 | 430 | 485 |
3×1×185 | 4.5 | 33.9 | 77.2 | 7328 | 0.0991 | 490 | 560 |
3×1×240 | 4.5 | 36.4 | 82.8 | 9113 | 0.0754 | 560 | 660 |
NFC 33-226Medium voltage cables (non-aerial) 8.7/15kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
3×1×50 | 4.5 | 25.5 | 58.6 | 2028 | 0.641 | 180 | 190 |
3×1×70 | 4.5 | 27.3 | 62.7 | 2379 | 0.443 | 220 | 235 |
3×1×95 | 4.5 | 29.0 | 66.4 | 2748 | 0.320 | 260 | 290 |
3×1×120 | 4.5 | 30.7 | 70.1 | 3115 | 0.253 | 300 | 330 |
3×1×150 | 4.5 | 32.3 | 73.1 | 3476 | 0.206 | 335 | 375 |
3×1×185 | 4.5 | 33.9 | 77.2 | 3955 | 0.164 | 380 | 430 |
3×1×240 | 4.5 | 36.4 | 82.8 | 4676 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 8.7/15kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
3×1×50 | 5.5 | 28.0 | 63.4 | 3180 | 0.387 | 230 | 245 |
3×1×70 | 5.5 | 29.5 | 67.5 | 3932 | 0.268 | 280 | 305 |
3×1×95 | 5.5 | 31.2 | 71.2 | 4804 | 0.193 | 335 | 375 |
3×1×120 | 5.5 | 32.9 | 74.9 | 5639 | 0.153 | 385 | 425 |
3×1×150 | 5.5 | 34.5 | 77.9 | 6530 | 0.124 | 430 | 485 |
3×1×185 | 5.5 | 36.1 | 82.0 | 7701 | 0.0991 | 490 | 560 |
3×1×240 | 5.5 | 38.6 | 87.6 | 9511 | 0.0754 | 560 | 660 |
NFC 33-226 Medium voltage cables (non-aerial) 12/20kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
3×1×50 | 5.5 | 28.0 | 63.4 | 2316 | 0.641 | 180 | 190 |
3×1×70 | 5.5 | 29.5 | 67.5 | 2685 | 0.443 | 220 | 235 |
3×1×95 | 5.5 | 31.2 | 71.2 | 3071 | 0.320 | 260 | 290 |
3×1×120 | 5.5 | 32.9 | 74.9 | 3455 | 0.253 | 300 | 330 |
3×1×150 | 5.5 | 34.5 | 77.9 | 3830 | 0.206 | 335 | 375 |
3×1×185 | 5.5 | 36.1 | 82.0 | 4328 | 0.164 | 380 | 430 |
3×1×240 | 5.5 | 38.6 | 87.6 | 5074 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 12/20kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
3×1×50 | 8.0 | 33.1 | 75.2 | 3979 | 0.387 | 230 | 245 |
3×1×70 | 8.0 | 34.9 | 79.2 | 4777 | 0.268 | 280 | 305 |
3×1×95 | 8.0 | 36.8 | 83.4 | 5725 | 0.193 | 335 | 375 |
3×1×120 | 8.0 | 38.3 | 86.6 | 6565 | 0.153 | 385 | 425 |
3×1×150 | 8.0 | 39.9 | 89.6 | 7491 | 0.124 | 430 | 485 |
3×1×185 | 8.0 | 41.5 | 93.7 | 8707 | 0.0991 | 490 | 560 |
3×1×240 | 8.0 | 44.0 | 99.3 | 10579 | 0.0754 | 560 | 660 |
NFC 33-226 Medium voltage cables (non-aerial) 18/30kV ABC FOR OVERHEAD DISTRIBUTION LINES-Copper Conductor
Number of cores × Cross-section | Nominal thickness of Insulation | Min. outer diameter over sheath | Twisted diameter of cable | Approx. weight | Max. DC resistance at 20ºC | Current rating Underground |
Current rating In air |
No.×mm2 | mm | mm | mm | kg/km | Ohm/km | A | A |
3×1×50 | 8.0 | 33.1 | 75.2 | 3115 | 0.641 | 180 | 190 |
3×1×70 | 8.0 | 34.9 | 79.2 | 3530 | 0.443 | 220 | 235 |
3×1×95 | 8.0 | 36.8 | 83.4 | 3992 | 0.320 | 260 | 290 |
3×1×120 | 8.0 | 38.3 | 86.6 | 4381 | 0.253 | 300 | 330 |
3×1×150 | 8.0 | 39.9 | 89.6 | 4790 | 0.206 | 335 | 375 |
3×1×185 | 8.0 | 41.5 | 93.7 | 5334 | 0.164 | 380 | 430 |
3×1×240 | 8.0 | 44.0 | 99.3 | 6143 | 0.125 | 440 | 510 |
NFC 33-226 Medium voltage cables (non-aerial) 18/30kV ABC FOR OVERHEAD DISTRIBUTION LINES–Aluminium Conductor
We are China Hta S26 Extruded XLPE Insulation Medium Voltage Cable NFC33-226 Standard manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Henan Jinshui Wire & Cable Co. Products
Cable Building Electrical Wires Made in China
2*6AWG+1*6AWG AAC Conductor ABC Aerial Bundle Overhead Cable
Manufacture 2 Core Cable 0.75mm PVC Flexible Cable Power Cable
Flexible Rubber Electrical Welding Cable with Ce
Round Wire Copper Conductor Flexible Welding Cable
Rubber Sheath or PVC Sheath Welding Cable Factory Prices
Popular Ltd. Products
600/1000V BS 5467 4core 185mm2 Underground Cable Steel Wire Armoured XLPE Power Cable
Yjv32 Yjv72 600/1000V Underground XLPE Copper Cable Armoured Power Cable
Nylon Cable Thhn/Thwn Electrical Wire 8mm 10mm 25 mm 30mm Building Wire 450/750V 90º C
70mm2 Flexible Copper Double Insulation Welding Cable for Welding Machine Price
Copper or Aluminum Conductor Low Voltage Power Transmission Electric Cable
Popular Medium Voltage Cable Products
Medium Voltage Cable XLPE Insulated Power Cable with Rated Voltage 3.6/6kv-26/35kv Mv ABC Cable
11 Kv N2xsy XLPE Insulated PVC Sheath Power Cable European Standard
Mv Underground Power Cables Outdoor Energy IEC 60502 BS 6622- 3.6/6kv
Popular Overhead Cable Products
Aluminium Conductor HDPE 1X95 XLPE Insulated Overhead ABC Mv Aerial Bundled Cable
Aluminum Core ABC Cable Medium Voltage Cable Multiple Core
Bare AAAC Conductor 6201 Astmb399 1/0AWG 7/3.37mm
Aluminum Core ABC Cable Medium Voltage Cable Multiple Core
Aerial Bunched Cables Overhead Application and XLPE Insulation Material ABC Cable
Bull 1/0AWG+1/0AWG Duplex Service Drop Cable ABC Cable
Tags: Henan Jinshui Wire & Cable Co., Ltd., Medium Voltage Cable, Overhead Cable