Durable Medium Voltage Power Cable with Al/XLPE/PVC Insulation

Durable Medium Voltage Power Cable with Al/XLPE/PVC Insulation image
Get Latest Price Request a quote
You May Like
Product Details
Product Description
5KV to 46KV Medium Voltage Cable
Application: Medium voltage power cables are apply for power transmission and distribution line at AC rated voltage up to 46kV.
Applicable standards: IEC60502-2, BS6622, SANS1339, AS/NZS1429.1, DIN VDE 0276-626, NFC 33-226, IEC60840, ICEA S-93-639,ICEA S-94-649, HD620,CSA C68.10or the standards agreed by both of the customers and us.
Construction:
Conductor: IEC60228 class 1 class 2 bear copper/Aluminum etc
Conductor Screen: Semi-conducting compound
Insulation: XLPE or EPR
Insulation Screen: Semi-conducting compound
Core: 1core or 3cores
Shield: Copper wire/ Copper tape/AL plastic tape/Aluminum tape
Inner Sheath( optional): PVC PE LSZH CPE
Armoured ( optional): Galvanized steel wire/Aluminum wire/Two layers of Aluminum tapegap-wrapped /Two layers of steel tape gap-wrapped / Galvanized steel interlocked armour/Aluminum alloy interlocked armour
Outer Sheath: PVC PE LSZH CPE
3.6/6KV XLPE Insulated aluminum wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
1×25 | 2.5 | 23.8 | 866 | 715 | 0.727 | 1.20 | 140 | 163 | 108 | 127 |
1×35 | 2.5 | 24.9 | 993 | 784 | 0.524 | 0.868 | 166 | 198 | 129 | 154 |
1×50 | 2.5 | 26.0 | 1152 | 867 | 0.387 | 0.641 | 196 | 238 | 152 | 184 |
1×70 | 2.5 | 27.7 | 1407 | 994 | 0.268 | 0.443 | 239 | 296 | 186 | 230 |
1×95 | 2.5 | 29.6 | 1721 | 1152 | 0.193 | 0.320 | 285 | 361 | 221 | 280 |
1×120 | 2.5 | 31.1 | 1994 | 1275 | 0.153 | 0.253 | 323 | 417 | 252 | 324 |
1×150 | 2.5 | 32.7 | 2301 | 1425 | 0.124 | 0.206 | 361 | 473 | 281 | 368 |
1×185 | 2.5 | 35.4 | 2804 | 1696 | 0.0991 | 0.164 | 406 | 543 | 317 | 424 |
1×240 | 2.6 | 38.0 | 3430 | 1976 | 0.0754 | 0.125 | 469 | 641 | 367 | 502 |
1×300 | 2.8 | 40.8 | 4119 | 2294 | 0.0601 | 0.100 | 526 | 735 | 414 | 577 |
1×400 | 3.0 | 44.4 | 5043 | 2706 | 0.0470 | 0.0778 | 590 | 845 | 470 | 673 |
1×500 | 3.2 | 49.8 | 6393 | 3398 | 0.0366 | 0.0605 | 735 | 958 | 578 | 767 |
1×630 | 3.2 | 53.9 | 7892 | 4024 | 0.0283 | 0.0469 | 831 | 1098 | 665 | 896 |
1×800 | 3.2 | 58.2 | 9719 | 4757 | 0.0221 | 0.0367 | 945 | 1266 | 761 | 1041 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
3.6/6KV XLPE Insulated steel wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Nominal Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
3×25 | 2.5 | 41.9 | 3207 | 2748 | 0.727 | 1.20 | 129 | 143 | 100 | 111 |
3×35 | 2.5 | 45.6 | 4054 | 3430 | 0.524 | 0.868 | 154 | 172 | 119 | 133 |
3×50 | 2.5 | 48.2 | 4654 | 3792 | 0.387 | 0.641 | 181 | 205 | 140 | 159 |
3×70 | 2.5 | 52.2 | 5592 | 4347 | 0.268 | 0.443 | 220 | 253 | 171 | 196 |
3×95 | 2.5 | 56.1 | 6703 | 4975 | 0.193 | 0.320 | 263 | 307 | 204 | 238 |
3×120 | 2.5 | 60.0 | 7762 | 5582 | 0.153 | 0.253 | 298 | 352 | 232 | 274 |
3×150 | 2.5 | 63.4 | 8878 | 6187 | 0.124 | 0.206 | 332 | 397 | 259 | 309 |
3×185 | 2.5 | 67.3 | 10248 | 6881 | 0.0991 | 0.164 | 374 | 453 | 293 | 354 |
3×240 | 2.6 | 73.5 | 12509 | 8072 | 0.0754 | 0.125 | 431 | 529 | 338 | 415 |
3×300 | 2.8 | 81.0 | 15741 | 10190 | 0.0601 | 0.100 | 482 | 599 | 380 | 472 |
3×400 | 3.0 | 88.8 | 19093 | 11996 | 0.0470 | 0.0778 | 541 | 683 | 432 | 545 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
18/30KV XLPE Insulated aluminum wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
1×35 | 8.0 | 37.4 | 1840 | 1630 | 0.524 | 0.868 | 170 | 201 | 132 | 158 |
1×50 | 8.0 | 38.7 | 2036 | 1751 | 0.387 | 0.641 | 200 | 242 | 156 | 190 |
1×70 | 8.0 | 40.4 | 2335 | 1920 | 0.268 | 0.443 | 242 | 300 | 190 | 235 |
1×95 | 8.0 | 42.3 | 2681 | 2112 | 0.193 | 0.320 | 288 | 363 | 224 | 285 |
1×120 | 8.0 | 43.8 | 2996 | 2278 | 0.153 | 0.253 | 326 | 420 | 256 | 328 |
1×150 | 8.0 | 46.4 | 3506 | 2621 | 0.124 | 0.206 | 364 | 476 | 286 | 372 |
1×185 | 8.0 | 48.3 | 3970 | 2862 | 0.0991 | 0.164 | 409 | 546 | 321 | 428 |
1×240 | 8.0 | 50.9 | 4661 | 3207 | 0.0754 | 0.125 | 472 | 645 | 372 | 505 |
1×300 | 8.0 | 53.5 | 5380 | 3555 | 0.0601 | 0.100 | 529 | 740 | 418 | 578 |
1×400 | 8.0 | 56.7 | 6333 | 3996 | 0.0470 | 0.0778 | 593 | 848 | 475 | 675 |
1×500 | 8.0 | 60.5 | 7556 | 4561 | 0.0366 | 0.0605 | 740 | 963 | 583 | 772 |
1×630 | 8.0 | 64.8 | 9172 | 5304 | 0.0283 | 0.0469 | 835 | 1101 | 675 | 900 |
1×800 | 8.0 | 69.1 | 11063 | 6101 | 0.0221 | 0.0367 | 950 | 1272 | 765 | 1046 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
||||||||||
18/30KV XLPE Insulated steel wire armour PVC sheath power cable | ||||||||||
Number of Cores and Nominal Area | Thickness of Insulation | Approx. Overall Diameter | Approx mass | Max. DC Resistance at 20ºC |
Current Rating | |||||
Copper | Aluminium | |||||||||
Copper | Aluminium | Copper | Aluminium | Direct In Soil | In air | Direct In Soil | In air | |||
Nos×mm2 | mm | mm | kg/km | kg/km | Ohm/km | Ohm/km | A | A | A | A |
3×35 | 8.0 | 72.1 | 7473 | 6848 | 0.524 | 0.868 | 154 | 175 | 118 | 132 |
3×50 | 8.0 | 76.2 | 9011 | 8149 | 0.387 | 0.641 | 180 | 210 | 139 | 158 |
3×70 | 8.0 | 80.3 | 10196 | 8951 | 0.268 | 0.443 | 217 | 258 | 171 | 200 |
3×95 | 8.0 | 84.4 | 11479 | 9751 | 0.193 | 0.320 | 261 | 310 | 204 | 240 |
3×120 | 8.0 | 88.0 | 12743 | 10563 | 0.153 | 0.253 | 296 | 353 | 229 | 279 |
3×150 | 8.0 | 91.2 | 13918 | 11228 | 0.124 | 0.206 | 332 | 405 | 256 | 310 |
3×185 | 8.0 | 95.3 | 15562 | 12196 | 0.0991 | 0.164 | 374 | 458 | 293 | 360 |
3×240 | 8.0 | 101.1 | 18038 | 13601 | 0.0754 | 0.125 | 429 | 535 | 338 | 420 |
3×300 | 8.0 | 106.2 | 20502 | 14952 | 0.0601 | 0.100 | 482 | 602 | 380 | 474 |
3×400 | 8.0 | 113.0 | 23898 | 16800 | 0.0470 | 0.0778 | 541 | 690 | 428 | 545 |
Trefoil arrangement;Maximum conductor temperature 90 °C ;Ambient air temperature 30 °C ;Ground temperature 20 °C ;Depth of laying 0,8 m ; Thermal resistivity of soil 1,5 K.m/W |
Products Pictures
Packing and loading containers pictures:
* We can design and produce ACSR according to client’s requirement. Any requirement, feel free to contact us!
Company Information
Certification
FAQ
1. Q:How does your factory control the quality?
A:Factory has a quick and enthusiastic merchandisers team, strict and responsible QC team, service for many well-known brands all around the world with our high-quality products and strict.
2. Q:Can I visit your company?
A: Sure,If you need,we will arrange the driver to pick you up.
3. Q:How can I get some samples?
A: Contact me on below,Determin sample and address for shipping.
4. Q:Have you ever supplied cables to our country?
A: Henway Cables have been sold to over 100 countries and regions in the world. you can contact me for details.
5. Q:What is your MOQ?
A: MOQ Normally 500 meters for big diameter cables. Please contact me for detail info if you have specific cable requirement.
6. Q:When can I get the price?
A: Usually quote within 6 hours after we get your inquiry.
7. Q:How long is your delivery time?
A: According to your order’s quantity. Usually our lead time is 3 – 20 working days.
For more information about wires and cables, please feel free to contact us. Your inquiries will be replied to within 6 hours!!
We are China Durable Medium Voltage Power Cable with Al/XLPE/PVC Insulation manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 18kv Cable Products
18/30 (36) Kv, Al XLPE Swa PVC 3X95mm2 XLPE Cable Underground
18/30 (36) Kv, Al XLPE Swa PVC 3X70mm2 Cable
18/30 (36) Kv XLPE Insulated PVC Sheathed Unarmoured Power Cable
18/30 (36) Kv, Al XLPE Swa PVC 3X300mm2 Cable
18/30 (36) Kv, Al XLPE Swa PVC 3X185mm2 Underground Cable
33kv Single Core Copper Aluminum XLPE Awa PVC Underground Cable
Popular 30kv Cable Products
18/30 (36) Kv Copper/ Aluminum Conductor Single Core XLPE Insulated Cts Awa Armored Cable
18/30 (36) Kv Copper/ Aluminum Conductor Three Core XLPE Insulated Cts Unarmored Cable
Popular Henway Electric Group Inc Products
2X16mm 2X6AWG Factory Price Hot Sales Aluminum Alloy Conductor Concentric Cable
Low Voltage Copper Conductor 50mm Electric Armored Power Cable
Popular Products
18/30 (36) Kv, Al XLPE Swa PVC 3X95mm2 XLPE Cable Underground
18/30 (36) Kv, Al XLPE Swa PVC 3X70mm2 Cable
18/30 (36) Kv XLPE Insulated PVC Sheathed Unarmoured Power Cable
18/30 (36) Kv, Al XLPE Swa PVC 3X185mm2 Underground Cable
33kv Single Core Copper Aluminum XLPE Awa PVC Underground Cable
18/30 (36) Kv, Al XLPE Swa PVC 3X300mm2 Cable
Tags: 18kv Cable, 30kv Cable, Henway Electric Group Inc