AAC Aluminum Bare Conductor Hornet 19/3.25mm ASTM IEC DIN BS

AAC Aluminum Bare Conductor Hornet 19/3.25mm ASTM IEC DIN BS image
Get Latest Price Request a quote
You May Like
Product Details
Product Description
AAC Aluminum Bare Conductor Hornet 19/3.25mm ASTM IEC DIN BS
Applications:
Concentric lay stranded Aluminium Conductor ( AAC) is made up of one or more strands of hard drawn 1350 aluminum alloy. These conductors are used in low, medium and high voltage overhead lines. AAC has seen extensive use in urban areas where spans are usually short but high conductivity us required. The excellent corrosion resistance of aluminium has made AAC a conductor of choice in coastal areas. Because of its relatively poor strength to weight ratio, AAC had limited use in transmission lines and rural distribution because of long spans utilized.
The excellent corrosion resistance of aluminium has made AAC a conductor of choice in coastal areas.Although aluminium-to-copper connections can be made, it is better to use aluminium conductors for service connections, as various forms of covered cable are available for this purpose.
Advantage:
1. high Current Carrying Capacity
2. excellent resistance to corrosion
3. Ideal for use in coastal area
4. suitable for low & medium voltage lines in urban area
Standard
ASTM B231, BS215, IEC 61089, DIN 48201, BS EN 50182
IEC 61089 | ||||||
Code Name | Nominal | No./Nominal diameter of wires |
Approximate Overall Diameter |
Approximate Weight |
Nominal Breaking Load |
Nominal DC Resistance at 20°C |
mm2 | No./mm | mm | kg/km | KN | ohm/km | |
10 | 10 | 7/1.35 | 4.05 | 27.4 | 2 | 2.8633 |
16 | 16 | 7/1.71 | 5.13 | 43.8 | 3 | 1.7896 |
25 | 25 | 7/2.13 | 6.39 | 68.4 | 4.5 | 1.1453 |
40 | 40 | 7/2.70 | 8.1 | 109.4 | 6.8 | 0.7158 |
63 | 63 | 7/3.39 | 10.17 | 172.3 | 10.4 | 0.4545 |
100 | 100 | 19/2.59 | 12.95 | 274.8 | 17 | 0.2877 |
125 | 125 | 19/2.89 | 14.45 | 343.6 | 21.3 | 0.2302 |
160 | 160 | 19/3.27 | 16.35 | 439.8 | 26.4 | 0.1798 |
200 | 200 | 19/3.66 | 18.3 | 549.7 | 32 | 0.1439 |
250 | 250 | 19/4.09 | 20.45 | 687.1 | 40 | 0.1151 |
315 | 315 | 37/3.29 | 23.03 | 867.9 | 52 | 0.0916 |
400 | 400 | 37/3.71 | 25.97 | 1102 | 64 | 0.0721 |
450 | 450 | 37/3.94 | 27.58 | 1239.8 | 72 | 0.0641 |
500 | 500 | 37/4.15 | 29.05 | 1377.6 | 80 | 0.0577 |
560 | 560 | 37/4.39 | 30.73 | 1542.9 | 89.6 | 0.0515 |
630 | 630 | 61/3.63 | 32.67 | 1738.3 | 100.8 | 0.0458 |
710 | 710 | 61/3.85 | 34.65 | 1959.1 | 113.6 | 0.0407 |
800 | 800 | 61/4.09 | 36.81 | 2207.4 | 128 | 0.0361 |
900 | 900 | 61/4.33 | 38.97 | 2483.3 | 144 | 0.0321 |
1000 | 1000 | 61/4.57 | 41.13 | 2759.2 | 160 | 0.0289 |
1120 | 1120 | 91/3.96 | 43.56 | 3093.5 | 179.2 | 0.0258 |
1250 | 1250 | 91/4.18 | 45.98 | 3452.6 | 200 | 0.0231 |
1400 | 1400 | 91/4.43 | 48.73 | 3866.9 | 224 | 0.0207 |
1500 | 1500 | 91/4.58 | 50.38 | 4143.1 | 240 | 0.0193 |
ASTM B231/B 231M | |||||||
Code Name | Nominal Area |
No./Nominal diameter of wires |
Approximate Overall Diameter |
Approximate Weight |
Nominal Breaking Load |
Nominal DC Resistance at 20°C |
|
AWG or MCM | mm2 | No./mm | mm | kg/km | KN | ohm/km | |
Peachbell | 6 | 13.3 | 7/1.56 | 4.68 | 36.6 | 2.5 | 2.1477 |
Rose | 4 | 21.1 | 7/1.96 | 5.88 | 58.2 | 3.9 | 1.3606 |
Iris | 2 | 33.6 | 7/2.47 | 7.41 | 92.6 | 6 | 0.8567 |
Pansy | 1 | 42.4 | 7/2.78 | 8.34 | 116.6 | 7.3 | 0.6763 |
Poppy | 1/0.0 | 53.5 | 7/3.12 | 9.36 | 147.2 | 8.8 | 0.5369 |
Aster | 2/0.0 | 67.4 | 7/3.50 | 10.5 | 185.7 | 11.1 | 0.4267 |
Phlox | 3/0.0 | 85 | 7/3.93 | 11.79 | 233.9 | 13.5 | 0.3384 |
Oxlip | 4/0.0 | 107.2 | 7/4.42 | 13.26 | 295.2 | 17 | 0.2675 |
Valerian | 250 | 126.7 | 19/2.91 | 14.55 | 348.6 | 20.7 | 0.2274 |
Sneezewort | 250 | 126.7 | 7/4.80 | 14.4 | 348.8 | 20.1 | 0.2269 |
Laurel | 266.8 | 135.2 | 19/3.01 | 15.05 | 372.2 | 22.1 | 0.2125 |
Daisy | 266.8 | 135.2 | 7/4.96 | 14.88 | 372.3 | 21.4 | 0.2125 |
Peony | 300 | 152 | 19/3.19 | 15.95 | 418.3 | 24.3 | 0.1892 |
Tulip | 336.4 | 170.5 | 19/3.38 | 16.9 | 469.5 | 27.3 | 0.1686 |
Daffodil | 350 | 177.3 | 19/3.45 | 17.25 | 487.9 | 28.4 | 0.1618 |
Canna | 397.5 | 201.4 | 19/3.67 | 18.35 | 554.9 | 31.6 | 0.143 |
Goldentuft | 450 | 228 | 19/3.91 | 19.55 | 627.6 | 35 | 0.126 |
Syringa | 477 | 241.7 | 37/2.88 | 20.16 | 664.8 | 38.6 | 0.1192 |
Cosmos | 477 | 241.7 | 19/4.02 | 20.1 | 664.8 | 37 | 0.1192 |
Hyacinth | 500 | 253.3 | 37/2.95 | 20.65 | 696.8 | 40.5 | 0.1136 |
Zinnia | 500 | 253.3 | 19/4.12 | 20.6 | 697.1 | 38.9 | 0.1134 |
Dahlia | 556.5 | 282 | 19/4.35 | 21.75 | 775.8 | 43.3 | 0.1018 |
Mistletoe | 556.5 | 282 | 37/3.12 | 21.84 | 775.7 | 44.3 | 0.1016 |
Meadowsweet | 600 | 304 | 37/3.23 | 22.61 | 836.3 | 47.5 | 0.0948 |
Orchid | 636 | 322.3 | 37/3.33 | 23.31 | 886.9 | 50.4 | 0.0892 |
Heuchera | 650 | 329.4 | 37/3.37 | 23.59 | 907.4 | 51.7 | 0.0871 |
Flag | 700 | 354.7 | 61/2.72 | 24.48 | 975.8 | 57.1 | 0.0811 |
Varbena | 700 | 354.7 | 37/3.49 | 24.43 | 975.7 | 55.4 | 0.0812 |
Nasturtium | 715.5 | 362.6 | 61/2.75 | 24.75 | 998.5 | 58.4 | 0.0793 |
Violet | 715.5 | 362.6 | 37/3.53 | 24.71 | 998.5 | 56.7 | 0.0794 |
Cattail | 750 | 380 | 61/2.82 | 25.38 | 1046 | 60.3 | 0.0754 |
Petunia | 750 | 380 | 37/3.62 | 25.34 | 1046 | 58.6 | 0.0755 |
Lilac | 795 | 402.8 | 61/2.90 | 26.1 | 1110 | 63.8 | 0.0713 |
Arbutus | 795 | 402.8 | 37/3.72 | 26.04 | 1109 | 61.8 | 0.0715 |
BS 215 Part 1 | |||||||
Code name | Nominal | No./Nominal diameter of wires |
Sectional Area | Overall | Weight | Calculated Breaking Load | Max.D.C. Resistance at 20ºC |
mm² | No./mm | mm² | mm | kg/km | daN | Ω/Km | |
Midge | 22 | 7/2.06 | 23.33 | 6.18 | 64 | 399 | 1.227 |
Aphis | 25 | 3/3.35 | 26.44 | 7.22 | 74 | 411 | 1.081 |
Gnat | 25 | 7/2.21 | 26.85 | 6.63 | 73 | 459 | 1.066 |
Weevil | 30 | 3/3.66 | 31.56 | 7.89 | 86 | 486 | 0.9082 |
Mosquito | 35 | 7/2.59 | 36.88 | 7.77 | 101 | 603 | 0.7762 |
Ladybird | 40 | 7/2.79 | 42.8 | 8.37 | 117 | 687 | 0.6689 |
Ant | 50 | 7/3.10 | 52.83 | 9.3 | 145 | 828 | 0.5419 |
Fly | 60 | 7/3.40 | 63.55 | 10.2 | 174 | 990 | 0.4505 |
Bluebottle | 70 | 7/3.66 | 73.65 | 10.98 | 202 | 1134 | 0.3881 |
Earwig | 75 | 7/3.78 | 78.55 | 11.34 | 215 | 1194 | 0.3644 |
Grasshopper | 80 | 7/3.91 | 84.05 | 11.73 | 230 | 1278 | 0.3406 |
Clegg | 90 | 7/4.17 | 95.6 | 12.51 | 262 | 1453 | 0.2994 |
Wasp | 100 | 7/4.39 | 106 | 13.17 | 290 | 1600 | 0.2702 |
Beetle | 100 | 19/2.67 | 106.4 | 13.35 | 293 | 1742 | 0.2704 |
Bee | 125 | 7/4.90 | 132 | 14.7 | 361 | 1944 | 0.2169 |
Cricket | 150 | 7/5.36 | 157.9 | 16.08 | 432 | 2385 | 0.1818 |
Hornet | 150 | 19/3.25 | 157.6 | 16.25 | 434 | 2570 | 0.1825 |
Caterpillar | 175 | 19/3.53 | 185.9 | 17.65 | 511 | 2863 | 0.1547 |
Chafer | 200 | 19/3.78 | 213.2 | 18.9 | 587 | 3240 | 0.1349 |
Spider | 225 | 19/3.99 | 237.6 | 19.95 | 654 | 3601 | 0.1211 |
Cockroach | 250 | 19/4.22 | 265.7 | 21.1 | 731 | 4040 | 0.1083 |
Butterfly | 300 | 19/4.65 | 322.7 | 23.25 | 888 | 4875 | 0.08916 |
Moth | 350 | 19/5.00 | 373.1 | 25 | 1027 | 5637 | 0.07711 |
Drone | 350 | 37/3.58 | 372.4 | 25.06 | 1027 | 5745 | 0.07741 |
Locust | 400 | 19/5.36 | 428.7 | 26.8 | 1180 | 6473 | 0.0671 |
Centipede | 400 | 37/3.78 | 415.2 | 26.46 | 1145 | 6310 | 0.06944 |
Maybug | 450 | 37/4.09 | 486.1 | 28.63 | 1340 | 7401 | 0.05931 |
Scorpion | 500 | 37/4.27 | 529.8 | 29.89 | 1461 | 7998 | 0.05441 |
Cicada | 600 | 37/4.65 | 628.3 | 32.55 | 1732 | 9495 | 0.04588 |
Tarantula | 750 | 37/5.23 | 794.9 | 36.61 | 2192 | 12010 | 0.03627 |
BS EN 50182 | ||||||
Code Name |
Nominal Area |
No. / Dia. of Wire |
Approx. Overall Diameter | Approx. Weight |
Calculated Breaking Load | Max.DC Resistance at 20° C |
mm2 | No. / mm | mm | kg/km | kN | Ohm/km | |
Box | 18.8 | 7/1.85 | 5.55 | 51.4 | 5.6 | 1.748 |
Acacia | 23.8 | 7/2.08 | 6.24 | 64.9 | 7 | 1.3828 |
Almond | 30.1 | 7/2.34 | 7.02 | 82.2 | 8.9 | 1.0926 |
Cedar | 35.5 | 7/2.54 | 7.62 | 96.8 | 10.5 | 0.9273 |
Deodar | 42.2 | 7/2.77 | 8.31 | 115.2 | 12.4 | 0.7797 |
Fir | 47.8 | 7/2.95 | 8.85 | 130.6 | 14.1 | 0.6875 |
Hazel | 59.9 | 7/3.30 | 9.9 | 163.4 | 17.7 | 0.5494 |
Pine | 71.6 | 7/3.61 | 10.83 | 195.6 | 21.1 | 0.4591 |
Holly | 84.1 | 7/3.91 | 11.73 | 229.5 | 24.8 | 0.3913 |
Willow | 89.7 | 7/4.04 | 12.12 | 245 | 26.5 | 0.3665 |
Oak | 118.9 | 7/4.65 | 13.95 | 324.5 | 35.1 | 0.2767 |
Mulberry | 150.9 | 19/3.18 | 15.9 | 414.3 | 44.5 | 0.2192 |
Ash | 180.7 | 19/3.48 | 17.4 | 496.1 | 53.3 | 0.183 |
Elm | 211 | 19/3.76 | 18.8 | 579.2 | 62.2 | 0.1568 |
Poplar | 239.4 | 37/2.87 | 20.09 | 659.4 | 70.6 | 0.1387 |
Sycamore | 303.2 | 37/3.23 | 22.61 | 835.2 | 89.4 | 0.1095 |
Upas | 362.1 | 37/3.53 | 24.71 | 997.5 | 106.8 | 0.0917 |
Yew | 479 | 37/4.06 | 28.42 | 1319.6 | 141.3 | 0.0693 |
Totara | 498.1 | 37/4.14 | 28.98 | 1372.1 | 146.9 | 0.0666 |
Rubus | 586.9 | 61/3.50 | 31.5 | 1622 | 173.1 | 0.0567 |
Sorbus | 659.4 | 61/3.71 | 33.39 | 1822.5 | 194.5 | 0.0505 |
Araucaria | 821.1 | 61/4.14 | 37.26 | 2269.4 | 242.2 | 0.0406 |
Redwood | 996.2 | 61/4.56 | 41.04 | 2753.2 | 293.9 | 0.0334 |
As a leading manufacture in China,Our customers come from around the world,Welcome to visit us at any time!
Just leave your message if you are interested in our products,We will contact you very soon!
We are China AAC Aluminum Bare Conductor Hornet 19/3.25mm ASTM IEC DIN BS manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Henan Kingyear Aluminum Industrial Co. Products
BV BVV Rvvp Rvv VV VV22 VV32 Electric Power Cable
Overhead Single Core XLPE Insulated Aluminum ABC Cable 0.6/1kv
Low/Medium/High Voltage High Quality All Types ABC Cable for Brazil Chile Columbia
Electric Twist Cable Wire Soft 1.5 mm 2 Core Electrical Wire Blasting Wire Twin Twisted 2*1.5
Au Armoured Power Cable for Malaysia Brazil Market
329 Wire Electric Wire Cable Electric Wire 15mm2 6mm Heat Resistant Cable
Popular Hornet 19/3.25mm AAC Products
Popular Hornet AAC All Aluminum Conductor Products
Popular Ltd. Products
Transmission Power Line Qifan Reel and Drum Aluminum Conductor AAC 1350-H19
Hot Sale! Yh Yh-V Yhf H01n2d 120mm2 Flexible Rubber Welding Wire Cable
Medium Voltage XLPE Insulated Swa Armoured Underground Electrical Power Cable 500mm2 3.6/6kv
Low Voltage Copper Aluminum Conductor XLPE Insulated PE PVC Sheathed Sta Swa Electrical Power Cable
21/35kv PVC Sheath Underground Cable 3cx150sq. mm 3cx185sq. mm
Tags: Henan Kingyear Aluminum Industrial Co., Hornet 19/3.25mm AAC, Hornet AAC All Aluminum Conductor, Ltd.