600/1000V, Triplex Aluminum Service Drop Cable, 2/0AWG

600/1000V, Triplex Aluminum Service Drop Cable, 2/0AWG image
Get Latest Price Request a quote
You May Like
Product Details
Product Description
Triplex Aluminum Service Drop Cable
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
AAAC 6201 ALLOY FULL NEUTRAL MESSENGER | |||||||||||
Minex | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 101 | 101 | 85 | 70 |
Hippa | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 107 | 107 | 85 | 70 |
Prawn | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 152 | 152 | 115 | 90 |
Barnacle | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 160 | 160 | 115 | 90 |
Shrimp | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 243 | 243 | 150 | 120 |
Gammarus | 1/0 | 7 | 60 | 1/0 | 123.3 | 7 | 4460 | 390 | 390 | 205 | 160 |
Leda | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 384 | 384 | 205 | 160 |
Dunganese | 2/0 | 7 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
Cyclops | 2/0 | 11 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
Flustra | 3/0 | 17 | 60 | 3/0 | 195.7 | 7 | 6790 | 587 | 587 | 275 | 215 |
Lepas | 4/0 | 18 | 60 | 4/0 | 246.9 | 7 | 8560 | 728 | 728 | 315 | 245 |
*Code words for XLP insulated products are formed by adding “/XLP” to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
AAAC 6201 ALLOY REDUCED NEUTRAL MESSANGER | |||||||||||
Artemia | 4 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 135 | 135 | 115 | 90 |
Crab | 4 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 143 | 143 | 115 | 90 |
Solaster | 2 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 216 | 216 | 150 | 120 |
Sandcrab | 1/0 | 7 | 60 | 2 | 77.47 | 7 | 2800 | 347 | 347 | 205 | 160 |
Echinus | 1/0 | 9 | 60 | 2 | 77.47 | 7 | 2800 | 341 | 341 | 205 | 160 |
Crayfish | 2/0 | 7/w | 60 mls | 2/0 | — | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
Sipho | 2/0 | 7/w | 60 mls | 2/0 | — | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
Fulgar | 3/0 | 17 | 60 | 1/0 | 123.3 | 7 | 4460 | 519 | 519 | 275 | 215 |
Arca | 4/0 | 18 | 60 | 2/0 | 155.4 | 7 | 5390 | 643 | 643 | 315 | 245 |
*Code words for XLP insulated products are formed by adding “/XLP” to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+…………… | ||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
AAC NEUTRAL-MESSENGER | ||||||||||
Haiotis | 6 | 7/w | 45 mls | 6 | 7 | 563 | 109.1 | 101.6 | 85 Amps | 70 Amps |
Patella | 6 | 7 | 45 | 6 | 7 | 563 | 103 | 103 | 85 | 70 |
Fusus | 4 | 7/w | 45 mls | 4 | 7 | 881 | 161.8 | 151.7 | 115 Amps | 90 Amps |
Oyster | 4 | 7 | 45 | 4 | 7 | 881 | 154 | 154 | 115 | 90 |
Clam | 2 | 7 | 45 | 2 | 7 | 1350 | 233 | 233 | 150 | 120 |
Murex | 1/0 | 7 | 60 | 1/0 | 7 | 1990 | 374 | 374 | 205 | 160 |
Purpura | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 368 | 368 | 205 | 160 |
Nassa | 2/0 | 7 | 60 | 2/0 | 7 | 2510 | 462 | 462 | 235 | 185 |
Melita | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 562 | 562 | 275 | 215 |
Portunus | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 696 | 696 | 315 | 245 |
Nannynose | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 1118 | 1118 | 420 | 325 |
* Code words for XLP insulated products are formed by adding “/XLP” to the conventional code words above (e.g.-Haiotis/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
ASCR NEUTRAL-MESSENGER | ||||||||||
Paludina | 6 | 1 | 45 | 6 | 6/1 | 1190 | 109 | 109 | 85 | 70 |
Voluta | 6 | 7 | 45 | 6 | 6/1 | 1190 | 114 | 114 | 86 | 70 |
Whelk | 4 | 1 | 45 | 4 | 6/1 | 1860 | — | 164 | 115 | 90 |
Periwinkle | 4 | 7 | 45 | 4 | 6/1 | 1860 | 172 | 172 | 115 | 90 |
Conch | 2 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
Neritina | 1/0 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
Cenia | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 414 | 414 | 205 | 160 |
Runcina | 2/0 | 7 | 60 | 2/0 | 6/1 | 5310 | 520 | 520 | 235 | 185 |
Triton | 2/0 | 11 | 60 | 2/0 | 6/1 | 5310 | 512 | 512 | 235 | 185 |
Mursia | 3/0 | 17 | 60 | 3/0 | 6/1 | 6620 | 635 | 635 | 275 | 215 |
Zuzara | 4/0 | 18 | 60 | 4/0 | 6/1 | 8350 | 789 | 789 | 315 | 245 |
Limpet | 336.4 | 19 | 80 | 336.4 | 18/1 | 8680 | 1167 | 1167 | 420 | 325 |
*Code words for XLP insulated products are formed by adding “/XLP” to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
ASCR REDUCED NEUTRAL-MESSENGER | ||||||||||
Scallop | 4 | 1 | 45 | 6 | 6/1 | 1190 | — | 142 | 115 | 90 |
Strombus | 4 | 7 | 45 | 6 | 6/1 | 1190 | 151 | 151 | 115 | 90 |
Cockle | 2 | 7 | 45 | 4 | 6/1 | 1190 | 220 | 220 | 150 | 120 |
Janthina | 1/0 | 7 | 60 | 2 | 6/1 | 2853 | 366 | 366 | 205 | 160 |
Ranella | 1/0 | 9 | 60 | 2 | 6/1 | 2853 | 360 | 360 | 205 | 160 |
Cavolinia | 2/0 | 7 | 60 | 1 | 6/1 | 3550 | 453 | 453 | 235 | 185 |
Clio | 2/0 | 11 | 60 | 1 | 6/1 | 3550 | 444 | 444 | 235 | 185 |
Sanddollar | 3/0 | 19/w | 60 mls | 1/0 | 6/1 | 4380 | 565 | 552 | 275 Amps | 215 Amps |
Aega | 3/0 | 17 | 60 | 1/0 | 6/1 | 4380 | 549 | 549 | 275 | 215 |
Cuttlefish | 4/0 | 19/w | 60 mls | 2/0 | 6/1 | 5310 | 699 | 684 | 315 Amps | 245 Amps |
Cerapus | 4/0 | 18 | 60 | 2/0 | 6/1 | 5310 | 681 | 681 | 315 | 245 |
Cowery | 336.4 | 19 | 80 mls | 336/4 | 18/1 | 8680 | 1209 | 1167 | 420 Amps | 325 Amps |
*Code words for XLP insulated products are formed by adding “/XLP” to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
There is a lot of debate still going on as to whether copper is better for electrical purposes or aluminum. If price was not a critical factor, most would suggest going in for silver as it is said to be the best conductor of electricity but has a low strength. However, when it comes to electrical wiring, price is a factor, as is efficiency.
Applications:
To supply power from the utility’s lines to the consumer’s weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75°C maximum for polyethylene Insulation or 90°C maximum for crosslinked insulation.
Construction:
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR or 6201 alloy neutral messenger.
Standards:
B-230 Aluminum Wire 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474.
There is a lot of debate still going on as to whether copper is better for electrical purposes or aluminum. If price was not a critical factor, most would suggest going in for silver as it is said to be the best conductor of electricity but has a low strength. However, when it comes to electrical wiring, price is a factor, as is efficiency.
Our company
Yifang Electric group mainly specialized in wire&cables,including designment,production and sale.
Products are mainly covering low,medium,high voltage(1KV to 220KV) XLPE Insulated power cable,PVC insulated power cable,ABC cable,building cable control cable,rubber cable welding cable Etc.
Our XLPE cable can be manufactured according to the company’s specification which is equivalent to IEC 60502,IEC60332,IEC60754. Some indexes are superior to above international standard.
Our certificate
FAQ
1.Q:Are you a factory or trading company?
A: Manufacturing base in Henan ,China, with more than 500 workers.
2.Q:How can I visit there?
A: Sure,If you need,we will arrange the driver to pick you up.
3.Q:How can I get some samples?
A: Contact me on below,Determin sample and address for shipping.
4.Q:Have you ever supplied cables to our country?
A: Yifang Cables have been sold to over 100 countries and regions in the world. can you contact me for details.
5.Q:What is your MOQ?
A: MOQ Normally 500 meters for big diameter cables.Please contact me for detail info if you have specific cable requirement.
6. Q:When can I get the price?
A: Usually quote within 6 hours after we get your inquiry.
7.Q:How long is your delivery time?
A: According to your order’s quantity.Usually our lead time is 3 – 20 working days.
We are China 600/1000V, Triplex Aluminum Service Drop Cable, 2/0AWG manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 2/0AWG Products
Triplex Service Drop, ABC Cable, 2/0AWG, Cyclops Lt Aerial Bunch Cable Ab 1100V
PAC, Parallel Aerial Cable, 2/0AWG
AAAC 2AWG, 4AWG, 2/0AWG, 4/0AWG Overhead Bare Conductor Astmb399
Overhead Cable High Voltage 15-35kv ACSR 1/0AWG, 2/0AWG, 3/0 AWG, 4/0 AWG, 336.4 Mcm Tree Wire
Popular Aluminum Cable Products
0.6/1kv Single Core Aluminum Concentric Cable 16mm
AAAC Aluminum Cable Conductor Overhead ASTM Standard
600V Transmission Line Material Aluminium Conductor XLPE Insulated ABC Cable
Low Voltage Aluminum Conductor XLPE/PE Insulation Overhead Electric Cable
ABC Cable 70mm2 120mm2 Aluminum Conductor Aerial Wire
Popular Triplex Aluminum Service Drop Cable Products
Popular Triplex Service Drop Cable Products
Triplex Service Drop Cable Patella 6AWG AAC Neutral Messenger
AAC/AAAC Conductor Triplex Service Drop Cable XLPE Electric Cables
Overhead Aerial Bundle Triplex Service Drop Aluminum Cable
AAAC Conductor Current Carrying Capacity Triplex Service Drop Cable XLPE Cable
Tags: 2/0AWG, Aluminum Cable, Triplex Aluminum Service Drop Cable, Triplex Service Drop Cable